  • Page 1 Manual Electrode Steam Humidifier Electrode Steam Humidifier...
  • Page 2 Because of this you should monitor your new unit during initial operation. Make sure that it has been properly installed and is operating to your satisfaction. Consult your HygroMatik specialists. We will test the quality of your water and advise you on installation and initial operation. Your HygroMatik steam humidifier will be carefully adapted to your particular application.
  • Page 3: Table Of Contents

    1. Introduction ........................5 1.1 Directions for Use ......................5 1.2 Typographic Distinctions ....................6 1.3 Documentation ........................7 2. Safety Notes ........................8 2.1 Overview ........................... 8 2.2 Guidelines for Safe Operation ................... 8 2.3 Disposal after Dismantling ....................9 3.
  • Page 4 6.3 Water discharge ........................ 38 6.4 Water Installation Check ....................39 7. Electrical Connection ......................40 7.1 Electrical Installation ......................40 7.2 Cable Connections ......................42 7.3 Fan Unit ..........................43 7.4 Safety Interlock ........................44 7.5 Wiring Diagram ........................44 7.6 Electrical Installation Checklist ..................
  • Page 5: Introduction

    They will impress you with their safety, ease of use and econom- ical operation. In order to operate your HygroMatik steam humidifier safely, properly and efficiently, please read these operating instructions. Employ your steam humidifier only in sound condition and as directed.
  • Page 6: Typographic Distinctions

    C2: Range of high conductivity (adjustments recommended) D2: Upper threshold Warning: HygroMatik steam humidifiers emit steam with a tem- perature of 100° C. The steam may not be inhaled directly. The HygroMatik Steam Humidifier is not designed for outdoor fit- ting 1.2 Typographic Distinctions ...
  • Page 7: Documentation

    If the product is resold, turn the documenta- tion over to the new operator. If the documentation is lost, please contact HygroMatik. Versions in Other Languages These operating instructions are available in several languages. If interested, please contact HygroMatik or your HygroMatik dealer. Page 7...
  • Page 8: Safety Notes

    2. Safety Notes 2.1 Overview These safety notes are required by law. They promote work- place safety and accident prevention. Warnings and Safety Symbols The safety symbols below identify sections containing warnings about hazards or potential dangers. Please familiarize yourself with these symbols.
  • Page 9: Disposal After Dismantling

    HygroMatik steam humidifiers are IP20-protected. Make sure that the unit is protected from drips in its installed location. Installing a humidifier in a room without water discharge requires safety devices to protect against water leakages. Accident Prevention Regulations Comply with the accident prevention regulationAccident Preven- tion Regulation Electrical Systems and Equipment to prevent injury to yourself and others.
  • Page 10: Transport

    3. Transport 3.1 Overview Note: Proceed carefully when transporting the steam humidifier in order to prevent damage due to stress or careless loading and unloading. 3.2 Carton outer Size and Weight HyLine: Type* Height Width Depth Weight [cm] [cm] [cm]...
  • Page 11: Packing

    Unit of the selected humidifier type including selected control.  Water installation hose 0,6m, 3/4".  Mounting set with anchors and screws. For HyLine types HY45 to HY116, extra mounting bar.  Operating Instructions for the unit and the control. ...
  • Page 12: Operation And Installation

    4. Operation and Installation 4.1 Mode of Operation The HygroMatik steam humidifier utilizes the conductivity nor- mally present in tap water for steam production. Electrodes inside an enclosed steam cylinder are immersed directly into the tap water. They are connected to the alternating current.
  • Page 13 Please also see Section „Exploded View“. Location Designation adapter vent pipe max. water level sensor electrode water drain, discharge top part of steam cylinder o-ring cylinder flange cylinder flange and o-ring lower part of cylinder solenoid valve water inlet blow-down pump o-ring cylinder base electrodes...
  • Page 14 The concentration of dissolved salts increases over time, which can lead to a rise in the conductivity of the water. If this contin- ues, conductivity may increase until a short circuit occurs. This could damage the unit, but in any case would significantly reduce the life span of the electrodes.
  • Page 15: Installation

    The minimum clearances indicated in the diagram below must be observed; these are necessary to ensure adequate ventilation for the housing.  HygroMatik humidifiers are not suitable for direct out- door installation.  The steam humidifier should be installed as close as possible to the steam manifold.
  • Page 16: Fitting Measures

    5.1.1 Fitting measures Clearances Note: When choosing the site for the steam humidifier, consider the location of existing water installations (feed and drain lines). Mounting Fixtures (for HY45 to HY116) The unit should be mounted on a stable wall. Note: To achieve a uniform immersed surface area for the elec- trodes, the humidifier must be installed plumb and level.
  • Page 17 to Install Units Type HY05- HY30: » Place the steam humidifier in its intended location, use a level to adjust position, and secure. See chapter "Unit Dimensions". » Attach the unit to the lower mounting fixtures. to Install Units HY45- HY116: »...
  • Page 18: Unit Dimensions Hy05-Hy45

    5.1.2 Unit Dimensions HY05-HY45 View from below Rear view View from top Type / Dimensions HY05-HY08 481 449 216 415 438 43 35 120 120 103 HY13-HY23 654 520 284 486 619 63 38 210 152 136 HY30 710 560 327 515 665 58 38 250 172 156 197 106 HY45...
  • Page 19: Unit Dimensions Hy60-Hy116

    5.1.3 Unit Dimensions HY60-HY116 Type / Dims. a d1 d2 d3 HY60 712 927 336 327 371 95 133 680 67 195 525 186 HY90-HY116 792 1061 404 398 398 132 132 758 67 238 635 220 Type / Dims k1 n3 n4 HY60 157 488...
  • Page 20: Fan Unit (Optional)

    5.2 Fan Unit (optional) Note: The fan unit should be positioned to avoid drafts. In gen- eral, a minimum height of 2 m is sufficient. Install the fan unit directly on a wall. Fan Unit Type for wall installation VG 08, 17, 30 Warning: ...
  • Page 21: Fan Unit Cover

    5.2.2 Fan Unit Cover Covers (optional) for Types HY05 and HY30 are available to pro- tect the steam and condensate hoses between the steam humidifier and the fan unit. The vertical distance between the humidifier and the fan unit is determined by the height of the cover (see Table of Dimensions H).
  • Page 22: Absorption Distance Bn

    5.3 Absorption Distance B The "absorption distance" (B ) is defined as the distance from the steam feed to where the steam is completely absorbed in the treated air. Inside the absorption distance, steam is visible as mist in the air stream. Condensation may collect on anything installed inside the absorption distance.
  • Page 23 Length I of the usable steam manifold depends on the dimen- sions of the air duct. The length of the absorption distance can be reduced by using multiple steam manifolds (also see section on the steam manifold). Method: Graphically determine absorption distance B using the absorp- tion distance nomogram (also see Section „Absorption Distance Nomogramm“...
  • Page 24: Absorption Distance Nomogram

    5.3.2 Absorption Distance Nomogram Source: Henne, Erich: Luftbefeuchtung (Air Humidification), 3 Edition 1984 (Page 101), Olden- bourg Industrieverlag, Munich Page 24...
  • Page 25: Steam Manifold

    5.4 Steam Manifold 5.4.1 Notes on Installation These notes are based on a homogeneous Horizontal installation of Standard steam manifold installation: steam manifold Duct Steam Manifold Air flow direction L1=L2=L3 An even distribution of steam manifolds ensures a uniform steam distribution.
  • Page 26 Air duct Positioning of steam manifolds Sample flat Staggered vertically and laterally Air flow very flat By tilting the steam manifold 30 - 45° very flat duct towards the air flow direction, the mini- mum upper clearance can be reduced to 70mm.
  • Page 27 With high-pressure air-conditioning systems, the unit's drain hose system must be modified depending on the over pressure. When this is the case please consult HygroMatik. • Install the steam manifold as close as possible to the steam humidifier in order to minimize steam loss through condensation.
  • Page 28 2x(1xDN40) 2x(1xDN12) * For units HL 6 - 12 HygroMatik delivers one adapter DN40 / 25.** For units HL 36 - 45 HygroMatik delivers one t-connector for separating the steam on two steam manifold. ***Hl 60.-90 are double units and consist of Hl 30-45 units.
  • Page 29: Steam Line

    Note: When installing the steam hose, please pay attention to the following: • The steam hose diameter may not be smaller than the steam outlet of the HygroMatik steam humidifier (do not restrict the cross-section, otherwise back pressure will increase). •...
  • Page 30: Cover Plate

    5.6 Cover Plate HygroMatik flange plates may be used to neatly complete instal- lation of the steam humidifier in the air duct. Two-piece flange plates are available for the DN25 and DN40 steam manifolds. flange plate DN25 E-2604260 flange plate DN40 E-2604410...
  • Page 31: Drill Pattern

    5.7 Drill Pattern Drill Pattern not to scale DN25 ( Note: Due to variable print media the dimensions are not to scale. Page 31...
  • Page 32 Drill Pattern not to scale DN40 ( Note: Due to variable print media the dimensions are not to scale. Page 32...
  • Page 33: Condensate Hose

    5.8 Condensate Hose Note: When installing the condensate hose, please pay atten- tion to the following: Warning: To keep condensate from accumulating in the duct, make sure condensate can drain freely. If the s team m anifold i s positio ned hig her than 5 00 mm above the steam humidifier: »...
  • Page 34 » If enough space is available, lay a loop as a vapor trap. The steam manifold must be at least 500 mm from the loop. If the ste am ma nifold is position ed lower than 5 00 mm above the steam humidifier: »...
  • Page 35: Steam Solenoid Valves

    5.10 Steam Solenoid Valves When humidifying a number of loads, which are to be controlled separately, using a single steam humidifier, steam solenoid valves can be included in the steam hoses. Valve control has to provided by the customer. • Install the vertical risers with flow from bottom to top.
  • Page 36: Water Installation

    Foam comes into contact with the maximum water level sensor electrode and triggers a signal indicating the cylinder is filled to capacity, even though this is false and the nominal current has not yet been reached. Note: Please contact HygroMatik if you wish to operate the unit Page 36...
  • Page 37: Water Supply

    Install a water filter (WF) if water quality requires it. Note: Shut-off valve (SV) and water filter (WF) are not supplied with the unit » HygroMatik provides a water hose (56) with a cap nut at both ends which can be used for water installation. Install as follows: »...
  • Page 38: Water Discharge

    6.3 Water discharge min.: 250mm max.: 1000mm Warning: During blow down hot water with a temperature of about 95°C is being drained. If touched this can cause burns to the skin. Warning: Water must drain freely! During blow down up to 0,3 litre water per second are being drained.
  • Page 39: Water Installation Check

    6.4 Water Installation Check Go down the following water installation checklist:  Are all screws and clamps properly tightened?  Is the water supply pipe flushed?  Was the water installation correctly installed?  Can the blow-down water drain freely? ...
  • Page 40: Electrical Connection

    7. Electrical Connection Danger, Hazardous Voltage: All work related to electrical instal- lation to be performed by authorized personnel only (electricians or professionals with equivalent training). The customer is responsible for checking qualifications. Danger, Hazardous Voltage: Do not plug the steam humidifier into the power grid until after all installation work has been com- pleted.
  • Page 41 We recommend employing medium blow main fuses (applicable only to the grid voltages above). See table below indicating max- imum power usage for each circuit protection: When using fault current circuit breakers please use a separate one for the humidifier. HyLine: Type Power Usage Circuit Protection HY05...
  • Page 42: Cable Connections

    MiniSteam: Type Power Usage Circuit Protection MS5, 230V/1/N 15,7 A 1 x 16 A MS5, 400V/3/N 5,4 A 3 x 6 A MS10, 400V/3/N 10,8 A 3 x 16 A DBE: Type Power Usage Circuit Protection DBE 2 6,5 A 1 x 10 A DBE 6 6,5 A...
  • Page 43: Fan Unit

    7.3 Fan Unit » Connect fan unit according to the wiring diagram. The fan unit operates in parallel with the humidifier. Note: Terminals 37 and 38 are only installed if the option „fan unit“ is ordered. Page 43...
  • Page 44: Safety Interlock

    Is the unit grounded? After this check the unit can be switched on. Warning: The unit must be closed and locked. This guarantees that the cover is grounded. (only humidifier type HyLine and MiniSteam) Note: For initial operation, control, service, malfunctions, and circuit diagrams, consult the operation instructions for the Hygro- Matik-controls.
  • Page 45: Commissioning

    8. Commissioning Warning: This unit is only to be started by qualified personnel. Switching off steam humidifier Warning: Before starting up the unit, make sure you know how to switch it off. » Switch off unit by setting control switch to “0” »...
  • Page 46: Maintenance

    9. Maintenance The HygroMatik steam humidifier is easy to maintain. However, inadequate or improper maintenance can lead to operational malfunctions. Perform regular maintenance to give your unit a long life span. Warning: When performing maintenance work, please note:  During operation and also for a while after switching off the unit the steam cylinder is hot.
  • Page 47: Access Electrical Enclosure

    In extreme cases, water pretreatment may be necessary (soft- ening by dilution to approx. 4 - 8 °dH; decarbonization/partial desalination to achieve target reductions in carbonate hard- ness). HygroMatik would be pleased to refer you to companies specializing in water treatment systems. 9.2 Access Electrical Enclosure »...
  • Page 48: Removing And Cleaning The Steam Cylinder

    9.3 Removing and Cleaning the Steam Cylinder Warning: Please follow the detailed instructions in these operat- ing instructions! The unit is only to be serviced by qualified, authorized personnel. Note the warnings and safety notes in the operating instructions. Failure to observe warnings and safety notes may result in injury, serious injury or death, and/or dam- age to the unit.
  • Page 49 Page 49...
  • Page 50 Warning: Check the inside of the top part of steam cylinder for crust build-up and possible salt bridges (black grooves between the electrode leads). If present, wash away completely . Note: If electrical arcs have burned deep grooves in the mate- rial, the top part of the cylinder must be replaced.
  • Page 51 Note: When putting the cylinder back together, the joints and reinforcements of both sections must fit together snugly. Page 51...
  • Page 52 Warning: Before attaching the electrode plugs please make sure that they are free of corrosion. If not please replace them. The plug must be pressed down onto the electrode as far as it will go. Note: Connect plugs to the correct electrodes. Note the color of the knurled nut.
  • Page 53: Electrode Wear

    Warning: The unit must be closed and locked. This guarantees that the cover is grounded. (Only with hymidifier type HyLine and MiniSteam) Switch on the unit and check for leaks after 15-30 minutes of operation. 9.4 Electrode wear Electrode wear depends on: ...
  • Page 54: Original Electrode Lengths

    The humidifier switches itself off. Also see Section "Mainte- nance." When the electrodes are less than 1/3 to 1/2 of their original length, replace them. 9.4.1 Original Electrode Lengths Original lengths of HygroMatik large area stainless-steel elec- trodes are: HyLine: Type...
  • Page 55 » Loosen knurled nuts (5) and remove electrodes (48). » Install new electrodes and hand tighten the nuts. Use solvent-free, HygroMatik-quality o-rings (for flange, cylinder base and steam hose adapter). » Assemble steam cylinder and place it into cylinder »...
  • Page 56: Cleaning The Blow- Down Pump

     there is "lightning" in the cylinder, the conductivity of the water is too high or it isn't decanted often enough. In this case please contact HygroMatik. 9.6 Cleaning the Blow- Down Pump » Remove cylinder »...
  • Page 57: Cleaning The Water Inlet Solenoid Valve

    9.7 Cleaning the Water Inlet Solenoid Valve Removal » Shut off water supply and loosen water installation hose connection. » Remove cylinder please also see chapter „Removing and Cleaning Steam Cylinder“ » Loosen connecting hose (21) from the base. » Detach e-cable from the solenoid valve.
  • Page 58: Checking Hoses

    9.9 Checking Hoses Since steam and condensate hoses are also subject to wear they have to be checked regularly. 9.10 Checking Operation Start up the unit and operate for a few minutes at maximum out- put if possible. » Check safety devices. »...
  • Page 59: Ec-Declaration Of Conformity

    10. EC-Declaration of Conformity Page 59...
  • Page 60: Spare Parts

    11. Spare Parts HY05 HY13 Description Articel No. HY08 HY17 HY23 HY30 HY45 HY60 HY90 HY116 Keys for safety, set=2pc. E-2124010 Safety lock incl. 2 keys E-2124012 Steam generation B-3204031 Steam cylinder CY8 compl. with electrodes and hand nuts ** B-2204231 Steam cylinder CY8 DN40 compl.
  • Page 61: Water Drain

    HY05 HY13 Articel No. Description HY08 HY17 HY23 HY30 HY45 HY60 HY90 HY116 Mounting set for Cylinder base B-3216023 Condensate cap DN12 E-2204035 E-3221002 Adapter for steam hose DN25, CY8 E-3221008 Adapter for steam hose DN40, CY8, for SPA applications since 04.2010 Adapter for steam hose DN25, CY17 E-2209000...
  • Page 62 HY05 HY13 Articel No. Description HY08 HY17 HY23 HY30 HY45 HY60 HY90 HY116 O-ring for pump-adapter E-3220005 O-ring for cylinder base -pump E-3220005 E-2404024 O-ring for drain pump (cover-motor) Drain pump without mounting set B-2404027 B-2424014 Mounting set for drain pump (pos. 42-44) Elbow with vent pipe E-2425004 E-2420423...
  • Page 63 HY05 HY13 Articel No. Description HY08 HY17 HY23 HY30 HY45 HY60 HY90 HY116 Control, electrical supply higher than 500V E-2504158 Transformer 690V/230V, 25VA Transformer 480V-500V/230V E-2504168 E-2504160 Transformer 600V/230V Transformer 690V/230V, 130VA E-2504166 E-2590102 Line safety switch, 1 A Control, electrical supply between 416V and 480V E-2507024 Main Contactor 60A, 230V/690V...
  • Page 64 HY05 HY13 Articel No. Description HY08 HY17 HY23 HY30 HY45 HY60 HY90 HY116 Temperature sensor TF104 E-0605228 B-2505207 Holder for temperature sensor TF104 incl. mounting set E-2505206 Fuse for light, fan, essence injector 1.6A, 5x20mm E-2504039 Fuse for transformer 5A, 5x20mm E-2504200 Transformer 230/24V/130VA Essence injection...
  • Page 65: Fax Form - Order For Spare Parts

    12. Fax Form - Order for spare parts Fax Form Please copy, fill in and fax to Lise-Meitner-Str. 3 . +49(0)4193/895-31 Fax.No 24558 Henstedt-Ulzburg Tel. +4904193/895-0 Order of spare parts unit type *______________ serial no.* ___________________ commission: ______________ order no.: __________________ quantity article article no.
  • Page 66: Technical Specification

    13. Technical Specification Technical Specifications Steam Humidifier HyLine Type HY05 HY08 HY13 HY17 HY23 Steam output [kg/h] Power supply * 400V/3~/N/50-60 Hz Power Usage [kW] 12,8 17,3 Input [A] 14,1 18,4 24,9 Circuit Protection [A]*** 3x10 3x16 3x20 3x35 Control...
  • Page 67 Technical Specification Technical Specifications Steam Humidifier HyLine for SPA HY05..-DS - HY23..-DS Type HY05 HY08 HY13 HY17 HY23 Steam output [kg/h] Power supply * 400V/3~/N/50-60 Hz Power Usage [kW] 12,8 17,3 Input [A] 14,1 18,4 24,9 Circuit Protection [A]*** 3x10...
  • Page 68: Exploded View

    14. Exploded View Page 68...
  • Page 69: View Of Housing

    15. View of housing Page 69...
  • Page 70 Lise-Meitner-Str.3 D-24558 Henstedt-Ulzburg Phone +49(0)4193/ 895-0  Fax -33 eMail hy@hygromatik.de  www.hygromatik.com 12/2004 A member of the Group...