Connecting the DC Cables

Copper Compression Lug
Figure 2-3 DC cable lug examples
2–8
Consult
Figure 1-1, "Configuration for Normal Loads" on page
Figure 1-2, "Configuration for Heavy Loads" on page 1–3
details that are specific to your installation.
To make the DC connections:
1. Cut the cables to the correct length with enough insulation stripped
off so you can properly install the type of terminals you will be using.
The terminals on the DC end are designed to fit up to 500 MCM
crimp-on ring terminals (either AMP or ILSCO) or box connectors.
2. Attach the connectors to both cables.
If using compression lugs, attach the terminals to both cables using
the crimp tool recommended by the manufacturer of the ring
terminals. There must be no stray wire strands protruding from
the terminal. If using box lugs, attach the lug to the
3000
first, then insert the wire and tighten the set screw to the torque
recommended by the lug manufacturer.
3. Route the DC supply cables from the battery bank to the inverter.
This guide for use by qualified installers only.
Do not place anything
between battery cable lug
and terminal surface.
Assemble exactly as shown.