975-0556-01-01
7. Install a strain-relief device (not provided) on the AC knockout.
8. Run each of the line, neutral, and ground wires through the knockout
and through the strain-relief device.
9. Loosen the screws on the left side of the terminal block, if not already
loose at the factory. Be careful not to loosen the right side screws.
terminal block screws
Figure 2-2 Terminal Block
10. Insert the ground (bare or green) wire into the terminal block's
(G)round connector.
11. Secure the wire by tightening the ground terminal block screw to a
maximum torque of 16 inch-pounds (1.8 Nm).
12. Insert the Line (black) and Neutral (white) wires into the terminal
block's (L)ine and (N)eutral connectors, respectively.
13. Secure the wires by tightening the line and neutral terminal block
screws to a maximum torque of 16 inch-pounds (1.8 Nm).
WARNING: Shock hazard
Exposed and uncapped wires are a shock hazard. If you cut the wires after
permanently connecting the AC output wires make sure that you terminate the
wires with a proper wire cap terminal.
14. Complete the installation of the strain-relief device.
15. Replace the
Inverter 3000
using the screws from step #4.
16. Connect the outgoing AC wires to the AC load panel.
This guide for use by qualified installers only.