Faults Displayed On Hydraulic Unit - Fujitsu 112 Installation And Operating Manual

Heat pump air/water split single service 3 phase
Hide thumbs Also See for 112:
Table of Contents

Advertisement

Heat pump split single service 3 phase
6 2

Faults displayed on hydraulic unit

Faults or breakdowns on the hydraulic mode are
indicated by the display on the user interface.
Hydraulic unit : Fault visible on the digital display.
Error number Error contents
-
No connection.
10
Outdoor sensor.
33
Heat pump initial temperature sensor error.
44
Heat pump return temperature sensor error.
50
DHW temperature sensor.
60
Ambient temperature sensor 1.
65
Ambient temperature sensor 2.
105
Maintenance message.
121
Flow temperature for (HC1) not reached.
122
Flow temperature for (HC2) not reached.
127
Anti-legionella temperature not reached.
369
External fault (safety component).
Outdoor unit connection error
370
(In the start phase, see the para. "Start-up").
Hydraulic unit : Flashing of the diode visible on the interface card.
Diodes display
LED 2 (green)
1 Flash
4 Flashes
4 Flashes
6 Flashes
6 Flashes
7 Flashes
7 Flashes
7 Flashes
7 Flashes
7 Flashes
7 Flashes
8 Flashes
8 Flashes
9 Flashes
9 Flashes
9 Flashes
10 Flashes
10 Flashes
10 Flashes
Continuous flashing (1 sec On / 1 sec Off)
Continuous lighting
Installation and operating manual "1364 - EN"
Error contents
LED 1 (red)
1 Flash
Communication error between Hydraulic unit and Outdoor unit.
1 Flash
Heat pump capacity signal error (Open or short).
2 Flashes
Hydraulic unit heat-exchange thermistor Error.
3 Flashes
Inverter error.
Active filter error.
4 Flashes
PFC error.
1 Flash
Discharge thermistor error.
2 Flashes
Compressor thermistor error.
Heat-exchange thermistor (outlet) error.
3 Flashes
Heat-exchange thermistor (intermediate) error.
4 Flashes
Outdoor thermistor error.
Heat sink thermistor (inverter) error.
7 Flashes
Heat sink thermistor (P.F.C.) error.
8 Flashes
Expansion valve thermistor error.
4 Flashes
Current sensor error.
Pressure sensor error.
6 Flashes
Pressure switch error.
4 Flashes
Current trip.
Detection of compressor position error.
5 Flashes
Compressor start up error.
7 Flashes
Outdoor unit fan motor error.
1 Flashes
Discharge temperature protection.
3 Flashes
Compressor temperature protection.
5 Flashes
Low pressure abnormal.
Pump down operation.
Off
Defrosting.
The display shows the "Bell" symbol
Press the Info key
for more details on the origin of
the fault.
When the error has been resolved, the faults are
re-initialised at zero automatically.
Error location
Failure to comply with room
thermostat's polarity.
B9
B21
B71
B3
See
page 54.
.
Heat pump operation
despite the error
No
Yes with OT = 0 °C
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
- 53 -