Fujitsu 112 Installation And Operating Manual page 36

Heat pump air/water split single service 3 phase
Hide thumbs Also See for 112:
Table of Contents

Advertisement

Heat pump split single service 3 phase
Line
Function
Cooling circuit 1
901
U
Operating mode
902
U
Comfort cooling setpoint
907
U
Release
908
I
Flow temp setp at OT° 25°C
909
I
Flow temp setp at OT° 35°C
912
I
Cooling limit at OT°
913
S
Lock time at end of heating
918
S
Summer comp start at OT°
919
S
Summer comp end at OT°
920
S
Summer comp setp increase
923
S
Flow temp setp min OT° 25°C
924
S
Flow temp setp min OT° 35°C
928
S
Room influence
If the installation is fitted with an room sensor :
This function enables you to choose the ambient temperature's influence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
932
S
Room temp limitation
938
S
Mixing valve decrease
941
S
Actuator running time
945
S
Mixing valve in heating mode
946
S
Lock time dewpoint limiter
947
S
Flow temp setp incr hygro
948
S
Flow setp incr start at r.h.
S
950
Flow temp diff dewpoint
963
S
With prim contr / system pump
*Basic setting : 1 circuit = No ; 2 circuits = Yes
969
S
Operating mode changeover
Heating, Circuit 2 (Only with the 2
If the installation consists of 2 heating circuits
1010
U
Comfort heating setpoint
1012
U
Reduced setpoint
1014
U
Frost protection setpoint
1016
S
Comfort setpoint max
1020
I
Heating curve slope
1021
I
Heating curve displacement
1026
S
Heating curve adaption (see
- 36 -
circuit kit option)
nd
(figure 41)
§
3.3.2)
Setting range
or display
Off, Automatic
17... 40 °C
24h/day, Time program HC,
Time program 5 / Refresh
6... 35 °C
6... 35 °C
--, 8... 35 °C
--, 8... 100
20... 50 °C
20... 50 °C
--, 1... 10 °C
6... 35 °C
6... 35 °C
--, 1... 100 %
--, 0,5... 4 °C
0... 20 °C
30... 873 s
Control, Open
--, 10... 600 min
--, 1... 20 °C
0... 100 %
--, 0... 5 °C
No, Yes
No, Off, Automatic
from reduced setpoint to 35°C
from frost protection setpoint...
to comfort setpoint
from 4°C... to reduced setpoint
20... 35 °C
0,1... 4
-4,5... 4,5 °C
Off, On
Installation and operating manual "1364 - EN"
Setting
Basic
increment
setting
Off
0,5 °C
24 °C
Time
program 5
0,5 °C
20 °C
0,5 °C
16 °C
0,5 °C
24 °C
1 h
24 h
1 °C
26 °C
1 °C
40 °C
1 °C
4 °C
0,5 °C
18 °C
0,5 °C
18 °C
1 %
80 %
0,5 °C
0,5 °C
1 °C
0 °C
1 s
240 s
Control
10 min
60 min
1 °C
10 °C
1 %
60 %
2 °C
1 °C
No*
Off
0,5 °C
20 °C
0,5 °C
18 °C
0,5 °C
8 °C
1 °C
28 °C
0,02
0,5
0,5 °C
0
Off

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

140160