7.4 Check the Transmit – Receive indicators
This is a convenient way to check the presence of TX – RX signals:
If the Rx Led and the Tx Led never lit, the problem may come from:
If only the Tx Led never lit, the problem may come from:

7.5 Check the function called and the register addresses

To ensure that a read or write message to a Modbus address will produce a normal
response, check that the register address corresponds exactly to the desired data
requested.
In Modbus register addressing there are several categories of register, including holding
registers (numbered from 40001 upwards) and input registers (numbered from 30001
upwards). The category of register addressed is implicit in the Modbus function used, e.g.
function 03 addresses holding registers and function 04 addresses input registers.
Irrespective of the function used, the register address 30001 or 40001 would be
addressed in the transmitted message as register 0, 30002 or 40002 as register 1, 30010
or 40010 as register 9 and so on.
In the Modbus communications all these register addresses are not active and don't
contain valid information. A read or write to an unused register address will produce an
exception error.

7.6 Check the data access level and the limited range of data

To ensure that a write message to a Modbus address will produce a normal response,
check that the data value and access level is valid.
Writings in the controller memory though Modbus are restricted to the setting of some
access levels which need to be set. Look at:
18 – Troubleshooting  RS-485
Connection of a ground wire and presence of a shielding will improve reliability.
The Receive Led (yellow Led) indicates that a Modbus query is being received by
the RS485 Modbus adapter.
The Transmit Led (green Led) indicates that a Modbus response is being
transmitted from the RS485 Modbus adapter.
The wires of the RS485 cable are not properly fixed or cabled
The query is not sent (see the application software)
The controller and then the RS485 are not powered
The controller settings are not correct (check communication parameters
settings)
The controller entered the 'listen only' mode (reset the controller or send the
required command to disable the 'listen only' mode.)
o
The master sends Broadcast messages (address 0) which are to be
acted on by all connected devices and do not require a reply
SET MODE
LOCKING SWITCH
BANK SETTINGS