Mounting; Technical Data - ABB RS485 Installation And Startup Manual

Modbus adapter for rvt touchscreen
Hide thumbs Also See for RS485:
Table of Contents

Advertisement

4.3 Mounting

The Modbus adapter is specially shaped to fit the controller case and to plug into its
dedicated connectors without any other additional fixation part than just a screw.
3D view
Controller optical
transceiver

4.4 Technical data

Operating ambient temperature: -20 to +70 °C
Number of nodes (Tx drive): 32 max
Rx loading: receiver impedance is 1 unit load per RS485 Modbus adapter
Size of the Link: 247 stations including repeaters (31 stations and 1 repeater per
segment)
Medium: Shielded, twisted pair RS485 cable (Belden 9841 typical)
Maximum Bus Length: 1200 m
Topology: Multi-drop
Serial Communication Type: Asynchronous, 2 wires half Duplex
Baud rate: 110, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 bauds
selectable by the user (can be adjusted through the controller menus)
Termination resistor: built in, selectable by a switch. 120 ohms resistor is needed
at both end of the line and must be switched or not depending on the location in
the Modbus network topology.
Fixing screw
57 mm
TX – RX led's
35 mm
48 mm
Controller power
supply connector
Resistor
Termination switch
Extra depth to
the controller
max. 10 mm
3D view inserted in back plate
Screwed terminal for
bus cable connection
RS485  RS485 Modbus adapter - 11

Hide quick links:

Advertisement

Table of Contents
loading