Install Unit On Mounting Bracket; Outdoor Unit Installation; Locate Outdoor Unit; Clearances For The Outdoor Unit - Harbor Point HF-25GW Installation, Operation And Maintanance Manual

Wall split ductless cooling only and heat pump systems
Table of Contents

Advertisement

HARBOR POINT WALL SPLIT DUCTLESS SYSTEMS

Install unit on mounting bracket

Feed the line set stubs/condensate hose/
wiring connections through a ø 3" hole in
the wall.
Position the evaporator so that the "key"
slots on the back of the unit slide onto the
tabs on top of the mounting bracket. Then
push the lower portion of the evaporator
against the bracket until it latches into the
mounting bracket.
Indoor unit is now installed, it should be
plumb, level and flush with the wall. In-
sure that the line set stubs are completely

Locate Outdoor unit

Select a location with proper ventilation,
minimizing recirculation possibility. Do not
install the outdoor unit in a location ex-
posed to high winds (field fabricated and
installed wind baffle may be required).

Clearances for the Outdoor unit:

12" Minimum
Note: Consult factory if
minimum clearances can't
be maintained.
INDOOR UNIT INSTALLATION

OUTDOOR UNIT INSTALLATION

Outdoor Unit
Front
Condenser Fan
18,000 Btuh shown
through the wall penetration, also check
that the wall is plumb. The unit must be
level and plumb for proper condensate
removal.
Ensure location does not impede access
around unit and pose a disturbance to
neighboring areas.
Install the outdoor unit on a condenser
service pad. If unit is a heat pump ex-
tend feet to raise 6" to allow for defrost
to drain away.
12" Minimum
Airflow
48" Minimum
9
Service
Valves
Rear
12" Minimum