Heat Pump Wiring; Connection Of Wires For Outdoor Unit And Indoor Unit - Harbor Point HF-25GW Installation, Operation And Maintanance Manual

Wall split ductless cooling only and heat pump systems
Table of Contents

Advertisement

HARBOR POINT WALL SPLIT DUCTLESS SYSTEMS
If the system is a heat pump the defrost
sensor must be connected from the in-
door unit to the defrost sensor in the out-
door unit. Standard lead length is 25 ft,
if a longer length is required then cut the
lead and extend using thermostat wire.
The heat pump defrost sensor intercon-
nect wire comes bundled up with the indoor
units. It then should be "un-bundled" and
connected to the molex connection at the
indoor unit and run to the outdoor unit molex
connection, typically with the interconnect-
ing wiring and/or interconnecting tubing.
Defrost Sensor
Indoor wire connector
Ground wires connected to the terminal plate on indoor and
Connection of wires for outdoor
unit and indoor unit
(115V Models)
Outdoor
1 2 3 L1 N1
unit
Indoor
1 2 3 L1 N1
unit
(heating model)
(208/230V Models)
Outdoor
1 2 3 L3 L4
unit
Indoor
1 2 3 L3 L4
unit
(heating model)
OUTDOOR UNIT INSTALLATION

HEAT PUMP WIRING

outdoor probe wire connector
for defrosting
outdoor units must be grounded.
L N
To power
source
L1 L2
To power
source
Note: use of colored wire (supplied with
line set) and defrost sensor connected
(heat pump only).
Indoor sensor connection
Outdoor sensor connection
13