Evacuation; Main Power Wiring; Electrical Specifications - Harbor Point HF-25GW Installation, Operation And Maintanance Manual

Wall split ductless cooling only and heat pump systems
Table of Contents

Advertisement

HARBOR POINT WALL SPLIT DUCTLESS SYSTEMS

Evacuation

Gauges can now be attached to the service
ports - SERVICE PORTS HAVE A 5/16"
CONNECTION TO GAUGES, which is dif-
ferent from the norm for R-22. You will need
specific hoses or an adaptor for the 5/16"
connection.
Once the gauges are attached the line
set can be leak checked using Nitrogen
at 300 psig. Evacuate the unit and inter-
connect down to a minimum of 400-500
Microns, break vacuum with Nitrogen to
further leak check.
Re-evacuate the system down to 300-400
Microns or lower for a period of one hour.
This is an R-410A System it is essential
that a deep vacuum be pulled on the sys-
Nominal
Capacity
Volts/Hz/Ph
Btuh
9,000
115/60/1
12,000
115/60/1
18,000
208/230/60/1
24,000
208/230/60/1
9,000
115/60/1
12,000
115/60/1
18,000
220/60/1
24,000
208/230/60/1
A local disconnect should be installed ad-
jacent to the outdoor unit in accordance
with National and Local Codes. The out-
door unit provides power for the indoor
unit, no disconnect is required between
the outdoor and indoor units.
Line voltage from the disconnect should
be wired to:
N - L (115V Unit), + G
L1 - L2 (208/230V Unit), + G
Remove right side knockout on the termi-
nal access panel for whip/wiring connec-
OUTDOOR UNIT INSTALLATION
Electrical Specifications
Compressor
Cond Fan
RLA
LRA
Watts
Cooling Models Only
7.5
47
35
9.9
53
45
6.6
42
60
10.0
46
60
Heat Pump Models Only
7.5
47
35
9.9
53
45
6.6
42
60
10.0
46
60
11
tem to remove all traces of moisture. See
"System Start-Up" section to fine-tune the
refrigerant charge.

Main Power Wiring

Electrical wiring should be done in ac-
cordance with all National Electrical Code
(NEC) and local state/city building codes.
Note: A small screwdriver is required
for unit terminals.
Breaker size and wiring must be sized
for the rating plate amperage, MCA and
HACR. Use only HACR type breakers,
each system installed must have a sep-
arate branch
circuit with an individual
breaker/fuse.
Indoor Fan
RLA
Watts
RLA
0.81
16
0.35
0.80
16
0.35
0.85
40
0.40
0.90
40
0.40
0.81
16
0.35
0.80
16
0.35
0.85
40
0.40
0.90
40
0.40
tion. Ground connection must be made to
the terminal plate.
Heat Pump (208/230 V) unit terminals:
L1 - L2 : Power from breaker + G
L3 - L4 : Power to indoor unit + G
1 - 2 - 3 : Control signals
These are just examples of typical wiring
connections. Always refer to Wire Diagram
on unit for actual wiring connections.
Tip: For easier access to the terminals in the
outdoor unit remove the lower access panel to
install whip and sealtite connectors for conduit.
HACR
Total
MCA
Max
FLA
Fuse
7.2
10.6
15.0
9.6
14.0
20.0
6.4
9.5
15.0
8.1
13.8
23.8
7.2
10.6
15.0
9.6
14.0
20.0
6.4
9.5
15.0
8.1
13.8
23.8