I. Pre-Installation
WARNING
Carefully read all instructions before installing
boiler. Failure to follow all instructions in proper
order can cause personal injury or death.
A
. Installation must conform to the requirements of
the authority having jurisdiction. In the absence of
such requirements, installation must conform to the
National Fuel Gas Code, NFPA 54/ANSI Z223.1, and/
or CAN/CGA B149 Installation Codes. Where required
by the authority having jurisdiction, the installation
must conform to the Standard for Controls and Safety
Devices for Automatically Fired Boilers, ANSI/ASME
CSD-1.
B.
The boiler is not design certified for installation on
combustible flooring. The boiler must not be installed
on carpeting.
C.
Provide clearance between boiler jacket and combustible
material in accordance with local fire ordinance. Refer
to page 4 of this manual for minimum listed clearance
from combustible material.
D.
Install on level floor. For basement installation provide
concrete base if floor is not perfectly level or if water
may be encountered on floor around boiler. Floor
must be able to support weight of boiler, water and all
additional system components.
E.
Protect gas ignition system components from water
(dripping, spraying, rain, etc.) during boiler operation
and service (circulator replacement, condensate trap
service, control replacement, etc.).
F.
Provide combustion and ventilation air in accordance
with applicable provisions of local building codes or:
USA - National Fuel Gas Code, NFPA 54/ANSI Z223.1,
Section 5.3, Air for Combustion and Ventilation;
Canada - Natural Gas Installation Code, CAN/CGA
- B149.1, or Propane Installation Code, CAN/CGA
- B.149.2, Part 5, Venting Systems and Air Supply for
Appliances.
WARNING
Adequate combustion and ventilation air must
be provided to assure proper combustion.
The following guideline is based on the National Fuel
Gas Code, NFPA 54/ANSI Z223.1.
1. Determine volume of space (boiler room). Rooms
communicating directly with space (through
openings not furnished with doors) are considered
part of space.
Volume [ft³] = Length [ft] x Width [ft] x Height [ft]
2. Determine Total Input of all appliances in space.
Round result to nearest 1,000 Btu per hour (Btuh).
3. Determine type of space. Divide Volume by Total
Input.
a. If result is greater than or equal to 50 ft³ per 1,000
Btuh, space is considered an unconfined space.
b. If result is less than 50 ft³ per 1,000 Btuh, space is
considered a confined space.
4. Determine building type. A building of unusually
tight construction has the following characteristics:
a. Walls and ceiling exposed to outside atmosphere
have a continuous water vapor retarder with a
rating of 1 perm or less with openings gasketed
and sealed, and;
b. Weather-stripping has been added on openable
windows and doors, and;
c. Caulking or sealants applied in joints around
window and door frames, between sole plates and
floors, between wall-ceiling joints, between wall
panels, at plumbing and electrical penetrations,
and at other openings.
5. For boiler located in an unconfined space in a
building of other than unusually tight construction,
adequate combustion and ventilation air is normally
provided by fresh air infiltration through cracks
around windows and doors.
Boilers operated with sealed combustion are
exempt from needing provisions for combustion
air from the room, provided air intake piping is
installed per code and the instructions in this
manual.
For boiler located within unconfined space in
6.
building of unusually tight construction or within
confined space, provide outdoor air through two
permanent openings which communicate directly or by
duct with the outdoors or spaces (crawl or attic) freely
communicating with the outdoors. Locate one opening
within 12 inches of top of space. Locate remaining
opening within 12 inches of bottom of space. Minimum
dimension of air opening is 3 inches. Size each opening
per the following:
8
NOTICE