MCmultizone atomising humidifi ers User manual I n t e g r a t e d C o n t r o l S o l u t i o n s & E n e r g y S a v i n g s...
Page 3
The technical specifi cations shown in the manual may be changed without prior warning. The liability of CAREL S.p.A. in relation to its products is specifi ed in the CAREL S.p.A. general contract conditions, available on the website www.
14.4 Manifolds for installation in ducts ............42 5.9 Main menu ......................21 15. MAIN ADJUSTMENTS 6. USER MENU 6.1 Alarm thresholds ....................22 6.2 Clock ........................22 6.3 Enable scheduler ....................22 6.4 Set scheduler .......................22 6.5 Weekly scheduler ....................22 “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
Page 6
16. MAINTENANCE 16.1 Maintenance procedures ................44 16.2 Kits & optional accessories for the air/water line (see chap. 2) ..44 16.3 Kits & optional accessories for the atomising heads (see chap. 11) .......................44 16.4 Spare parts for air/water line (see paragraph 1.4) ......45 16.5 Pre-programmed pCO controllers .............46 16.6 Electrical panel kit and spare parts (see paragraph 1.4) ..46...
The MCmultizone system is essentially made up of: control cabinet and water and air inlet outlet (to nozzles) compressed air-water supply, atomising nozzles, nozzle assembly kit.
Terminal (Master version only) connection of the air and water distribution lines; Transformer (CAREL code MCKTR00000) power and control connections; Modulating valve regulator (modulating version only, CAREL code MCKARVA000) Important Important : the drain hose must be connected directly to a drain...
1.9 Opening the cabinet door press and turn anticlockwise using a fl at-head screwdriver (max 8 mm) until releasing the door; open the door on the cabinet by swinging to the left. “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
2. Install an oil fi lter (CAREL code MCFILOIL01) to remove particles of oil from the compressed air 3. Install a 5 micron air fi lter (CAREL code MCFILAIR01) upstream of the cabinet to solid particles from the compressed air.
0 to 2.5 bars • an expansion vessel (not supplied by Carel SpA) with a capacity of several litres, to avoid water hammer that may damage the installation. The water line is tested, and checked at a pressure of 0.35 bars downstream of the cabinet.
& limit humidity probe come from d. ambient humidity probe & limit humidity probe e. modulating control with temperature control f. mod. control with temperature control & limit probe Limit humidity probe External controller “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
+V term +(G) out T COM1 COM2 COM3 J 2 4 COM1 COM2 COM3 Contact open: MC unit off Contact closed: MC unit on ON/OFF humidistat MC cabinet ON/OFF humidistat ON/OFF COM1 shield “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
(J2) Cable shielded AWG 15/20 compressors Control to interface MC CAREL (for the codes of the probes see chap. 16.2 with: water treatment systems “Maintenance“) -0 to 4 bars/ 4 to 20 mA (-11 to power 500 VA Transducer: Electrical specifi...
Status and operation of Output specifi cations: maximum load 1 kΩ (10 mA) the contact: wash line enabled contact closed externally COM1 COM2 COM3 COM1 COM2 COM3 External contact for activating the wash function “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
> type of control > stop slave offl ine. AHU /Room 1 AHU /Room 1 AHU /Room 2 pLAN Master Slave 1 Slave 5 up to 5 Slave units Water & Air lines AHU - Air Handling Unit “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
In multizone mode, by disabling the “stop slave off line” function, if the pLAN is interrupted the slaves operate independently according to the signals from the probes or/and controllers. In this mode, the values will not be shown on the master display. “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
(stand alone) master unit connected to a pLAN network for multiple spaces master unit connected to a pLAN network for single spaces slave unit “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
ON/OFF or Modulating Type of op.. 6 (slave) bar/psi Press. sensor dd/mm/yy 00:00 Date & time Current: Network: Info (2/2) display Humidifi er model YES/NO In production Hours production dd/mm/yy 00:00 Date & time “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
Special func. (2/3) Washing Start washing Washing period Washing duration Enable fi lling Filling duration Special func. (3/3) Select main screen display Language Show language choice at start-up? 5. Supervisor Supervisor confi g. “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
Note: this screen is visible if “scheduler ON/OFF” has been enabled (see the enable scheduler screen). Setting of the intervals for the operation of the humidifi er over one day (24h): time band “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
For example, setting P4 each Monday (humidifi er off ), parameters Z1, Z2, Z3, Z4 (diff erent set point values) will not be observed, as the humidifi er is not programmed to operate on that day. “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
Show language choice at start- Limit probe Min value 0 to 100 %rH °C/ °F YES/NO confi g. Max value 0 to 100 %rH °C/ °F Off set -10 to 10 0 %rH °C/ °F “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
To modify the character in the space selected, use UP and DOWN, to confi rm the character and move to the next space press ENTER. “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
Alarm event description Log deleted Time hh:mm dd/mm/yy Date 8.2 System information (read only) information display Boot read only read only Bios read only Code read only Version read only Date “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
°C/°F Set point ON/OFF and modulating control share the ratio between the values, that is, the maximum signal applicable to the proportional solenoid valve corresponds to the rated production (Pnom). “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
Page 33
50% and 100% of rated production (Pnom). The activation hysteresis (default 0.2 °C) is indicated in Figure 4.2 as hy. Request Diff_Temp P. Max P. Min. Set point °C/°F “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
10.5 Drain/fi ll The production of atomised water depends on the reading of the Important: this function requires the installation of a CAREL NO temperature probe, with a second humidity probe (AO3) that limits drain solenoid valve at the end of the water line, available as an production, so as to limit the humidity level in the cooled air.
25 m 50 m system fl ow-rate l/h water water water water no. heads installed per type ID mm ID mm ID mm ID mm ID mm ID mm ID mm ID mm “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
Page 38
The diameters shown in the tables have been selected considering the use of a pair of connectors in each line, if the number of connectors doubles choose the next largest diameter. “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
3.35 m 4.90 m 5.4 l/h 4.6 m 0.90 m 3.65 m 5.20 m 6.8 l/h 6.1 m 1.20 m 4.00 m 6.10 m 10.0 l/h 9.4 m 1.50 m 4.60 m 7.00 m “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
Page 40
• humidity, limit and temperature probes, air line pressure sensor (optional) • water line drain solenoid valve (optional). Avoid running these cables near other power cables (electric motors, contactors, high voltage wires, etc...) “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
fi t the manifold outside the duct, with the ends of the nozzles spraying inside, as can be seen in Fig. 14.c. This saves around 20 cm. air flow Fig. 14.c “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
• With the pressure transducer, the cabinet automatically controls the pressure in the installation to the optimum value so as to compensate for any pressure drop in the line. “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
10 l/h. If the spray is visibly diff erent in intensity from the other similar heads, or the environmental conditions mean higher or lower absorption, the screw can be adjusted to increase or decrease the water fl ow-rate. This operation should only be performed by authorised personnel (CAREL service centres). Air and water line...
Atomising head assembly kit Atomising head mod. A 2.7 l/h Atomising head mod. B 4.0 l/h Atomising head mod. C 5.4 l/h Atomising head mod. D 6.8 l/h Atomising head mod. E 10 l/h “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
M C K M W 0 2 5 0 1 ON/OFF aggressive AW 0 to 2.5 bars water line 230 l/h UL M C K D S V W C 0 1 NO solenoid water valve AW 6 “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...
fl ow-rate of the cabinet. See points 8 and 9. CAREL reserves the right to modify the features of its products without prior notice. “MCmultizone” +030221981 - rel. 2.3 - 09.12.2014...