Check Method; Check Code List - Toshiba MiNi-SMMS MCY-MAP0501HT Service Manual

Mini-super modular multi system
Hide thumbs Also See for MiNi-SMMS MCY-MAP0501HT:
Table of Contents

Advertisement

10-2. Check Method

If an trouble occurs, the error code can be retrieved from the main remote controller/central remote controller (LCD
display) or the header unit interface P .C. board (7-segment display). Using this self diagnostic function, the trouble
can be identified using the table below.

Check code list

The following list shows all fault codes.
• If check code is from indoor remote controller: See "Main remote controller display" in the list.
• If check code is from outdoor unit: See "Outdoor 7-segment display" in the list.
• If check code is from AI-NET central control remote controller: See "AI-NET central control display" in the list.
• If check code is from indoor unit with wireless remote controller: See "Sensor display of receiving unit" in the list.
Check code
Outdoor 7-segment display
Wired
remote
controller
display
Auxiliary code
E01
E02
E03
E04
No. of indoor units in which
E06
E06
sensor has been normally
received
E07
E08
E08 Duplicated indoor addresses
E09
E10
01: Indoor/Outdoor
communication
E12
E12
02: Communication between
outdoor units
E15
E15
00: Capacity over
E16
E16
01 ~: No. of connected units
E18
00: Header is nothing
E19
E19
02: Two or more header units
01: Outdoor of other line
connected
E20
E20
02: Indoor of other line
connected
E23
E23
E25
E25
01: IPDU1 error
02: IPDU2 error
03: IPDU1, 2 error
E31
E31
04: Fan IPDU error
05: IPDU + Fan IPDU error
06: IPDU2 + Fan IPDU error
07: All IPDU error
IPDU: Intelligent Power Drive Unit
¡ : Lighting,
ALT.: Flashing is alternately when there are two flashing LED.
SIM: Simultaneous flashing when there are two flashing LED
Wireless remote controller
Sensor block display
of receiving unit
AI-NET central
control display
Timer Ready
Operation
¤
l
¤
l
¤
l
97
l
l
04
l
l
04
l
l
¤
l
96
¤
l
99
¤
l
CF
¤
l
42
l
l
42
l
l
89
¤
l
97, 99
l
l
96
l
l
42
l
l
15
l
l
15
l
l
CF
109
l
¤
: Flashing,
: Goes off
Check code name
Flash
l
Communication error between indoor and remote
controller (Detected at remote controller side)
l
Remote controller transmission error
l
Communication error between indoor and remote
controller (Detected at indoor side)
¤
Communication circuit error between indoor/outdoor
(Detected at indoor side)
¤
Decrease of No. of indoor units
¤
Communication circuit error between indoor/outdoor
(Detected at outdoor side)
l
Duplicated indoor addresses
l
Duplicated main remote controllers
l
Communication error between indoor MCU
l
Automatic address start error
¤
Indoor is nothing during automatic addressing
¤
Capacity over / No. of connected indoor units
l
Communication error between indoor units
¤
Outdoor header units quantity error
¤
Other line connected during automatic address
¤
Sending error in communication between outdoor units
¤
Duplicated follower outdoor addresses
¤
IPDU communication error
Detecting device
Remote controller
Remote controller
Indoor
Indoor
I/F
I/F
Indoor / I/F
Remote controller
Indoor
I/F
I/F
I/F
Indoor
I/F
I/F
I/F
I/F
I/F

Hide quick links: