Error detected by TCC-LINK central control device
Check code
Outdoor 7-segment display
Display on
central control
device
Check code Auxiliary code
C05
C06
C12
P30
Differs according to error contents of the with alarm
(L20 is displayed.)

Error detected by AI-NET central control device

Check code
Outdoor 7-segment display
Main remote
controller
Check code Auxiliary code
* These errors are concerned to communication of remote controllers (A, B) and central system [AI-NET X, Y], and the main remote controller displays [E01], [E02], [E03], [E09],
or [E18] in some cases and displays none in other cases according to the error.
Detected position
Check code name
AI-NET
central control
remote controller
TCC-LINK
TCC-LINK central control
device transmission error
TCC-LINK central control
device receiving error
HA control interface Interface batch alarm of
HA control interface
TCC-LINK
Follower unit error of
group control
Duplicated central control
address
Detected position
Check code name
AI-NET
central control
remote controller
97
AI-NET
AI-NET communication
system error
99
AI-NET
Duplicated network
adapters
b7
AI-NET
Error in indoor group
Error detection
Status
condition
Operation
Signal is not transmit from
• Check central control device error.
continued.
central control device.
• Check communication line error of central control device.
• Check setup of terminator resistor.
Operation
Signal is not received from
• Check central control device error.
continued.
central control device.
• Check communication line error of central control device.
• Check setup of terminator resistor.
• Check the power of connecting destination connected device.
• Check P .C. board error of the connected device.
Operation
Error was input in HA
• Check error input.
continued.
control interface
Operation
An error occurred in
• Check the error code of the unit with alarm.
continued.
follower unit of the group
control.
([P30] is displayed only on
the central remote
controller.)
Operation
Central control addresses
• Check the address setup.
continued.
were duplicated.
Error detection
Status
condition
Operation
E07/L07/L03/L08 was
• Check multiple network adapters.
continued.
detected when other
• Check wire and miscabling of remote controller: Only one network
indoor unit in the group
adapter can be connected to communication line of remote controller.
was defective.
Operation
Multiple network adapters
• Check communication line, miscabling, and power of indoor unit.
continued.
were connected to
• Check communication. (X, Y terminals)
communication line of
• Check network adapter P .C. board.
remote controller.
• Check the central controller (Central control remote controller, etc.)
(Detected at central
controller side)
Operation
Error of follower unit in the
• Check follower unit in the group.
continued.
group
Check item (position)