7-2-7. Operation Mode Selection Control

n Feature
This control can be operated with the operation mode which is permitted by SMC or SMH.
n Wiring
Input wiring
n Function / Electric wiring diagram
Outdoor unit
I/F P.C. board
SMC : Cooling mode designated input switch
SMH : Heating mode designated input switch
Terminal
COOL (SMC)
HEAT (SMH)
ON
OFF
OFF
OFF
OFF
∗1: "
(mode select control)" mark is indicated on the remote controller display.
• Be sure to prepare non voltage continuous point of contact for each terminal.
Size
3-core, 0.75 mm²
Connection
cable
CN510
Selected operation mode
Only cooling mode permitted
ON
Only heating mode permitted
Normal operation
Length
Up to 500 m
Shield wire
TCB-PCMO2E
COM
COOL
PJ17
HEAT
Shield
Note
∗1
∗1
CAUTION
75
Type
Local supply
SMC
SMH