Applied Control In Indoor Unit; Remote Location On/Off Control Box (Tcb-Ifcb-4E) - Toshiba MiNi-SMMS MCY-MAP0501HT Service Manual

Mini-super modular multi system
Hide thumbs Also See for MiNi-SMMS MCY-MAP0501HT:
Table of Contents

Advertisement

7-1-2. Applied Control in Indoor Unit

n Remote location ON/OFF control box (TCB-IFCB-4E)
[Wiring and setup]
• Use the exclusive connector for connection with the indoor control P .C. board.
• In a group control, the system can operate when connecting with any indoor unit (Control P .C. board) in the
group. However when taking out the operation/error signal from the other unit, it is necessary to take out from
each unit individually.
(1) Control items
1) Start/Stop input signal : Operation start/stop in unit
2) Operation signal
3) Error signal
(2) Wiring diagram using remote control interface (TCB-IFCB-4E)
Input
IFCB-4E : No voltage ON/OFF serial signal
Output
No voltage contact for operation, error display
Contact capacity: Below Max. AC240V 0.5A
Indoor control P.C. board
Start/Stop input
Remote controller prohibition/clear input
Operation signal output
Error signal output
: Output during normal operation
: Output during alarm
(Serial communication error or indoor/outdoor protective device) operation
1
COM (GND)
2
3
4
COM (+12V)
5
6
CN61
T10
(YEL)
Remote location ON/OFF control box
(TCB-IFCB-4E)
1
2
3
4
CN06
1
2
3
4
5
6
CN13
Power supply 220–240V,
220V,
66
ON/OFF serial
signal input
COM
Operation signal output
Error signal output
~
50Hz
~
60Hz

Hide quick links: