Floor Standing Type
Adjustment of air flow direction upwards/downwards
[In Cooling operation]
In cooling operation, move the flap with your hands so that the horizontal
air outlet points in a direction so that the cold air diffuses the entire room.
[In Heating operation (For Heat-pump model only)]
In heating operation, move the flap with your hands so that the horizontal
air outlet points in a downward direction, towards the floor.
Adjustment of air flow direction rightwards/leftwards
[In case of using unsymmetrical air directions]
Lift up the vertical flap lightly and direct it towards the desired
direction. Once completed lower the flap back down.
In this case, do not use the Swing function.
[In case of automatic swing]
1
SWING/FIX
Push the
button during operation.
• [SWING
] is displayed and the air direc-
tion will automatically change rightwards/
leftwards.
In cases where one remote controller
controls multiple indoor units, it is possible to
set each indoor unit individually, so that the
air flow direction can be altered.
2
SWING/FIX
Push the
button again while the
vertical flap is moving will allow you to
stop the louver in the desired position.
3
UNIT
Swing button
• To set up the air flow direction individually,
UNIT
push the
button to display each indoor
unit No. in a group control. Then set up the
air flow direction to the desired indoor unit.
• If there is no display, all the indoor units can
be operated collectively.
UNIT
• Every push of the
button, will change
the display as shown in the figure.
INFORMATION
• If cooling operation is performed with downward air outlet, dew may form on the surface of the cabinet
or the horizontal flap, resulting in possible dripping of water.
• If heating operation is performed with the horizontal air outlet actively moving, unevenness of the tem-
perature may increase in the room.
• Do not move the flap directly with your hands during swing operation; otherwise a fault may be caused.
The vertical flap does not stop immediately even if the
SWING/FIX
tion, push the
button.
2
1
In this case, do not use the
swing function.
TEMP.
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
FILTER
RESET TEST
SET CL
UNIT
1, 2
3
No display
Unit No. 1-1
Unit No. 1-2
Unit No. 1-4
Unit No. 1-3
SWING/FIX
button is pushed. To adjust the stop posi-

3-10. Timer Operation

A type of timer operation can be selected from the following three types.
OFF timer
: The operation stops when the time on the timer has reached the set time.
Repeat OFF timer : The unit will stop, every time the set time period has elapsed.
ON timer
: The unit will start when the time on the timer has reached the set time.
Timer operation
TEMP.
1
FILTER
RESET TEST
1
Push the TIMER SET button.
• The timer display (type) changes for every
push of the button.
• SET DATA and timer time displays flash.
2
Push the
TIME
buttons to select the "SET TIME".
For every push of the
button, the set time increases in the unit of 0.5 hr (30 minutes).
The maximum set time is 72.0 hr.
For every push of the
button, the set time decreases in the unit of 0.5 hr (30 minutes).
The minimum set time is 0.5 hr.
3
Push the SET button.
display disappears and timer time display goes on.
SETTING
When the ON timer is activated, the chosen time period will be displayed. Once the time has been
reached, all displays except the ON light will disappear.
Cancel of timer operation
4
Push the CL button.
• TIMER display will disappear.
• When the unit stops after the timer reached the preset time, the Repeat OFF timer will resume the
operation. However by pushing the
timer has again reached its set time.
45
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
2
SET CL
UNIT
3
4
OFF
OFF
(OFF timer)
(Repeat OFF timer)
No display
NOTICE
ON / OFF
button the repeat function will stop once the time on the
ON
(ON timer)