Appendix; Inverter Operation Mode - Mitsubishi Electric FR-V5NE-E Instruction Manual

Vector inverter
Table of Contents

Advertisement

APPENDIX

Inverter Operation Mode

(1)Operation mode switching conditions
Before switching the operation mode, check that:
1) The inverter is at a stop;
2) Both the STF and STR signals are off; and
3) The Pr. 79 "operation mode selection" setting is correct.
(For setting, use the inverter's operation panel or optional parameter unit.)
Pr. 79 Setting
0
PU or external operation
1
PU operation
2
External operation
3, 4
External/PU combined operation
5
Program operation
6
Switch-over
External operation
7
(PU operation interlock)
8
PU or external (signal switching)
REMARKS
When making a parameter setting using the Ethernet software, the operation mode needs to be switched to the
network operation mode. Set any of "0, 2, 6, 8" in Pr. 79 "operation mode selection" when changing the operation
mode to the network operation mode. (Refer to the inverter manual for details of Pr. 79.)
Operation Mode Selection
Switching to Network Operation Mode
Disallowed when the PU mode is selected. Allowed when
the external mode is selected.
Disallowed
Allowed
Disallowed
Disallowed
Allowed
Allowed only in the external operation mode when the
PU interlock signal (X12) is on.
Allowed only in the external operation mode (X16 on).
48