5-4 Interlocked Setting

Display the page needed to perform the G-50A interlocked setting by clicking [Initial Setting]-[Interlocked Setting]
in the setting menu pane. On this page, you perform the setting for the ventilator, which operates by interlocking
with the running and stopping of the indoor unit.
Click [Get from G-50A] to get data currently stored on the G-50A, or click [Set to G-50A] to send setting data to
the G-50A.
(1) From the [Interlocked LOSSNAY or OA processing unit] field, select, by clicking, the ventilator whose
run/stop operations you want to interlock with the run/stop operations of an indoor unit. To cancel a selection,
click it one more time and it will revert to being unselected.
(2) Select, by clicking, the indoor unit to operate with the ventilator from the [Air-conditioners operating with
LOSSNAY] field. To cancel a selection, click it one more time and it will revert to being unselected.
Note: A maximum of 16 indoor units can be registered to operate with one ventilator.
Get from G-50A
Read interlocked setting from G-50A.
-15-
Select Ventilator
Select the ventilator to be
interlocked.
Select Indoor Unit
Select indoor unit to operate with
ventilator.
Set to G-50A
Send interlocked setting to G-50A.