Mitsubishi Electric G-50A Operation Manual page 11

Air-conditioner network system central controller initial setting tool
Hide thumbs Also See for G-50A:
Table of Contents

Advertisement

5-1-2 Network Setting
In Network Setting, set the G-50A IP address, subnet mask and gateway address. If connecting to the G-50A via
a permanent LAN, consult with the network administrator before setting these addresses.
5-1-2-1 Settings for when the G-50A is connected to a dedicated LAN
(1) Enter the G-50A IP address in the [IP Address] field. If the LAN wiring has been newly set up, allocate IP
addresses to the G-50A units in a sequential order starting with [192.168.1.1]. For example the first G-50A
unit will receive an IP address of [192.168.1.1], the second G-50A unit will receive an IP address of
[192.168.1.2] and so on.
The Web Monitor PC that monitors G-50A and the Initial Setting Tool PC will also require network addresses
consistent with the rest of the LAN.
Note: When using a G-50A dedicated LAN, it is recommended to set the IP address as follows.
G-50A : Between [192.168.1.1] and [192.168.1.40]
Web Monitor PC : Between [192.168.1.101] and [192.168.1.150]
Initial Setting Tool PC : [192.168.1.201].
[ Example of IP address setting ]
G-50A No. 1
192.168.1.1
(2) Enter the G-50A subnet mask in the [Subnet Mask] field. Normally, you should enter [255.255.255.0].
(3) When monitoring remotely via a dial-up router, enter the router IP address in the [Gateway] field.
Leave the gateway address blank when not connecting via a dial-up router.
[ Example of a Remote Monitoring System ]
G-50A
IP Address :192.168.1.1
Subnet Mask :255.255.255.0
G/W Address :192.168.1.254
10BASE-T LAN straight cable
G-50A No. 2
192.168.1.2
Telephone line
Dial-up router
IP:192.168.1.254
Web Monitor PC
IP Address :192.168.1.101
Subnet Mask :255.255.255.0
G/W Address :Blank
Note: It is recommended to set the dial-up router IP address to [192.168.1.254]. Refer to
the dial-up router instruction manual for details of how to set the IP address.
Note: It is necessary to connect a modem (analog type or ISDN type) between the dial-up
router and telephone line when using a dial-up router which does not have a built-in
modem.
Hub
G-50A No. 3
192.168.1.3
Note: Some hubs have a dedicated port for connection with another hub.
Connect the G-50A and Web Monitor PC to the normal ports.
Telecommunication
Network
-9-
Web Monitor PC
Initial Setting Tool PC
192.168.1.101
192.168.1.201
Dial-up router, cellular phone etc.
Web Monitor PC
Initial Setting Tool PC

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents