D. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear-
ances as specifi ed. Framing or fi nishing material closer than
the minimums listed must be constructed entirely of non-
combustible materials (i.e., steel studs, concrete board, etc).
When installing a mantel, provisions must be made
in order to secure the mantel to the adjacent framing
materials. For example, lintel brackets or lag bolts may
be considered for this purpose.
Combustible Mantel Legs or Wall Projections
7 IN.
MIN.
FIREPLACE
14 IN. MIN.
OPENING
FACTORY-SUPPLIED
NON-COMBUSTIBLE BOARD
COMBUSTIBLE OR
NON-COMBUSTIBLE WALL
Figure 5.3 Combustible Mantel Leg and Wall Projections
Non-Combustible Mantel Legs or Wall Projections
NON-COMBUSTIBLE
SEE SECTION 13.E
FOR REQUIRED
CLEARANCES
FIREPLACE
OPENING
14 IN. MIN.
FACTORY-SUPPLIED
NON-COMBUSTIBLE
BOARD
Figure 5.4 Non-Combustible Mantel Leg and Wall Projections
1/2 IN. BUILDING MATERIAL
COMBUSTIBLE
COLUMN
4 IN.MAX.
1/2 IN. BUILDING MATERIAL
COLUMN
6 IN. MAX.
COMBUSTIBLE OR
NON-COMBUSTIBLE
WALL
Heat & Glo •
LUX36, LUX42 • 2287-900
Combustible Mantel Projections
1/2 IN.
NON-COMBUSTIBLE
MATERIAL
LUX36
LUX42
Note: All measurements in inches.
Note: Measurement is taken from top of the opening,
NOT the top of the fi replace.
Figure 5.5 Combustible Mantel Allowance
Non-Combustible Mantel Projections
1/2 IN.
NON-COMBUSTIBLE
MATERIAL
LUX36
LUX42
Note: All measurements in inches.
Note: Measurement is taken from top of the opening,
NOT the top of the fi replace.
Figure 5.6 Non-Combustible Mantel Allowance
• 2287-900 Rev. J
Rev. J
• 6/13
MAX.
12
9
6
21
3
MIN.
18
1
15
12
9
FIREPLACE
OPENING
MAX.
12
10
MIN.
21
18
6
1-1/4 IN.
SEE SECTION 13.D
FIREPLACE
OPENING
21