SECTION 3
WArNINg
3.5
Primary Input Connections
The PowerCut 1300/1600 consoles are equipped with approximately 10 ft. of 4-conductor input power cable for
3 phase connection. If single-phase connection is desired, cap the unused wire on the input power cable per
chart below. When operating this machine from a single-phase source, it must be connected to a dedicated 100
amp feed. Due to the higher input current requirements, the duty cycle of the machine is lower than in 3 phase
operation. See specification section or rating plate.
PRIMARY INPUT
POWER CABLE
ELECTrIC SHOCK CAN KILL! PrECAUTIONArY MEASUrES SHOULD
BE TAKEN TO PrOVIDE MAxIMUM PrOTECTION AgAINST ELECTrI-
CAL SHOCK. BE SUrE THAT ALL POWEr IS Off BY OPENINg THE LINE
(WALL) DISCONNECT SWITCH AND BY UNPLUggINg THE POWEr
COrD TO THE UNIT WHEN CONNECTIONS ArE MADE INSIDE Of THE
POWEr SOUrCE.
STANDArD UNITS
(NON-CE)
PHASE
3
1
L1
Black
Black
L2
Red
-
L3
White
White
GND
Green
Green
figure 3-1. Input Connections
CE UNITS
(EUrOPE)
PHASE
3
L1
Brown
L2
Black
L3
Gray
GND
Green/Yel
Green/Yel
INSULATE UNUSED POWEr COrD
CONDUCTOr WHEN CONNECTINg
CUSTOMER FUSED LINE DISCONNECT SWITCH
24
INSTALLATION
1
Brown
-
Gray
WArNINg
fOr SINgLE PHASE.
(See Table 3-1)