Storage; Function; Operating Modes; Operation With Mains Power Supply - AEG Protect 5.31 Series Operating Instructions Manual

10 kva-120 kva
Table of Contents

Advertisement

4.6

Storage

5

Function

5.1

Operating Modes

5.1.1

Operation with Mains Power Supply

Protect 5.31/xxx-480-220-120 10 kVA - 120 kVA
UPS units may only be stored for a maximum period of six months in
the original packaging in dry, ventilated rooms with a permanent roof.
The permissible ambient temperature range is between -35 °C and
+70 °C with a relative humidity of ≤ 85%.
If the unit is stored for longer than six months, conventional
desiccants must be added and the UPS units must be sealed in
airtight plastic film.
Please refer to the respective manufacturer's instructions for storage
instructions for the batteries.
Four different operating modes are possible:
Operation with mains power supply
Operation with faulty mains supply
Operation with defective inverter, and
operation with manual bypass.
SBS
Mains
circuit
Q29
~ _
Figure 8 Power circuit with mains supply
The rectifier is powered from the mains and converts the AC voltage
statically into a stabilised DC voltage. This DC voltage serves for
charging and automatic trickle charging of the connected battery,
which is always charged as a result.
The inverter converts this secured DC voltage into a stabilised
sinusoidal AC voltage and powers the connected loads.
Page 18 of 56
Secured
_
Q29
~
Q29 option
busbar
Loads
8000020680 BAL, en