Connection Cross Sections And Fuse Protection - AEG Protect 5.31 Series Operating Instructions Manual

10 kva-120 kva
Table of Contents

Advertisement

6.4

Connection Cross Sections and Fuse Protection

Layout of cross sections in acc. with
DIN 0298, Part 4, Table 3
Laying type B1/B2
1
Rectifiers, input
Rectifier fusing in A
2
Cross section in mm²/pole *1
3
SBS circuit input
SBS fusing in A
4
Cross section in mm²/pole *1
5
Load output
Load output fusing in A
6
Cross section in mm²/pole
7
Remote signalling
Cross section of the signal line
in mm²/pole
Battery
8
Battery connection
Battery fusing in A
9
Cross section in mm²/pole
Table 2
i
Protect 5.31/xxx-480-220-120 10 kVA - 120 kVA
X1
min.
max
X4
min.
max
X3
max.
min.
max.
X12
max..
X2
min.
max.
Connection cross sections and fuse protection
*
Laying of the PE conductor in accordance with VDE 0100 T540,
1
Table 6
NOTE:
The cable clamp rail is located 185 mm above the ground.
Observe the bending radius!
(With one bend: radius = 10 x diameter)
10
20
30
20
40
63
10
10
16
2x95
2x95
2x95
125
250
315
35
70
2x50
2x95
2x95
2x95
40
63
100
35
95
2x70
2x95
2x95
2x95
50
100
160
10
25
50
2x95
2x95
2x95
Page 29 of 56
Type rating in kVA
40
60
80
80
125
160
25
50
70
2x95
2x95
2x240
400
630
800
2x70
4x50
3x120
2x95
4x95
3x240
125
200
250
2x95
2x150
3x120
2x95
4x95
3x240
0,2 - 2,5
200
315
400
95
2x50
2x95
2x95
2x95
2x240
8000020680 BAL, en
100
120
200
250
95
2x50
2x185
2x185
1000
1250
4x150 4x240
315
400
4x150 4x240

Hide quick links: