Status/Measured Values - AEG Protect 5.31 Series Operating Instructions Manual

10 kva-120 kva
Table of Contents

Advertisement

Protect 5.31/xxx-480-220-120 10 kVA - 120 kVA
The operating display consists of 3 parts:
On the left-hand side, the unit status is shown in a pictogram. The
individual components of the unit are represented here as symbols.
The respective symbol flashes in the event of messages or faults in a
component. In addition, the current power circuit is indicated via a bar
diagram.
The centre part displays the most important measured values of
the unit in a digital as well as an analogue format. These values differ,
depending on the unit type. In this example, the capacity utilisation of
the individual phases (in this case, 3 phases) in percent and the
standby time are displayed as the most important measured values of
the unit.
The current display key assignment is displayed on the right-
hand side. Here you can switch the power converters on or off
depending on the unit status, as long as the operation has not been
blocked. You can also acknowledge the acoustic signal generator in
this area in the event of messages or faults. Use the bottom key with
the measuring device icon to call up menus with detailed information
on status and measured values.
Load L1-L3
Batt.
[%]
[min]
0
0
0
10
Figure 20 Operating display of the UPS with activated manual bypass
Using the manual bypass switch (option), you can disconnect the
unit from the load. The load is then supplied directly by the mains.
This state is shown on the display.
9.3.4

Status/Measured Values

You can access the Status/Measured values menu from the
operating display using the bottom key with the measuring device
icon. In this menu, you can select the statuses and measured values
of the circuits, battery, loads or communication options. The
"System" submenu displays the status of the UPS and the
individual components. If a fault occurs in a UPS component, you
can call up a detailed fault description in a submenu. After the
fault has been rectified, you must acknowledge the fault in this
menu.
If optional communication PCBs are installed in the unit, the "COM
interface" or "Remote signals" submenu displays the status of the
individual interfaces. Press the ENTER key in the respective
submenu to return to the "selection" menu.
Page 40 of 56
8000020680 BAL, en