INSTALLATION

NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your pri-
mary heat source. If you have a
central heating system, you may
run system's circulating blower
while using heater. This will help
circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
WARNING: A qualified ser-
vice person must install heater.
Follow all local codes.
WARNING: Never install the
heater
• in a bedroom or bathroom
• in a recreational vehicle
• where curtains, furniture, cloth-
ing or other flammable objects
are less than 42 inches from the
front, top or sides of the heater
• in high traffic areas
• in windy or drafty areas
CAUTION: This heater cre-
ates warm air currents. These
currents move heat to wall sur-
faces next to heater. Installing
heater next to vinyl or cloth wall
coverings or operating heater
where impurities (such as, but
not limited to, tobacco smoke,
aromatic candles, cleaning flu-
ids, oil or kerosene lamps, etc.) in
the air exist, may discolor walls
or cause odors.
8
IMPORTANT: Vent-free heaters add moisture to
the air. Although this is beneficial, installing heater
in rooms without enough ventilation air may cause
mildew to form from too much moisture. See Air
for Combustion and Ventilation, page 5.
CHECK GAS TYPE
Use the correct gas type (natural or propane/LP)
for your unit. If your gas supply is not correct, do
not install heater. Call dealer where you bought
heater for proper type heater.
is equipped for (natural or pro-
pane/LP) gas. Field conversion
is not permitted.
CLEARANCES TO COMBUSTIBLES
(Vent-Free Operation Only)
minimum clearances. If you can,
provide greater clearances from
floor, ceiling and adjoining side
and back walls.
Carefully follow the instructions below. This stove
is a freestanding unit designed to set directly on the
floor. IMPORTANT: You must maintain minimum
wall and ceiling clearances during installation. The
minimum clearances are shown in Figure 4, page 9.
Measure from outermost point of stove top.
Minimum Wall and Ceiling Clearances
(see Figure 4, page 9)
A. Clearances from outermost point of stove top
to any combustible side wall should not be
less than 12 inches.
B. Clearances from outermost point of stove top
to any combustible back wall should not be less
than 6 inches (Includes corner installations).
C. Clearances from the stove top to the ceiling
should not be less than 48 inches.
www.desatech.com
WARNING: This appliance
WARNING: Maintain the
111417-01B