Evolution
Mounting the new battery module
Carry out the above instructions in reverse order.
To ensure safety and high performance, use only batteries supplied by MGE Office Protection Systems.
Take care to firmly press together the two parts of the connector during remounting.
5.3

Replacing the Battery Module in the Rack Model

Safety recommendations
The battery can cause electrocution and high short-circuit currents. The following safety precautions are required before
servicing the battery components:
CAUTION: Do not dispose of batteries in a fire. The batteries may explode. Dispose of used batteries according to the instructions.
CAUTION: Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
CAUTION: A battery can present a risk of electrical shock and high short circuit current. The following precautions should be
observed when working on batteries:
a.
Remove watches, rings, or other metal objects.
b.
Use tools with insulated handles.
c.
Wear rubber gloves and boots.
d.
Do not lay tools or metal parts on top of batteries.
e.
Disconnect charging source prior to connecting or disconnecting battery terminals.
f.
Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground. Contact with
any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such
grounds are removed during installation and maintenance.
Battery-module removal
5 — 2
A. Remove the two screws on the left-hand side of the
front panel.
B. Disconnect the battery block by separating the two
connectors (never pull on the wires).
Maintenance
E N G L I S H
86-81700-00 A01