OWNER´S MANUAL

FREESTANDING INSTALLATIONS

HORIZONTALLY THROUGH WALL
( Refer to Figure 6)
12 INCHES
MINIMUN
NOTE: Follow L-Vent chimney manufacturer's instructions.
Position stove, adhering to clearances show in Figure Nº4
Locate position of hole in wall; directly behind stove exhaust vent.
Always maintain 3" clearance from combustible materials.
Install L-Vent wall thimble per L-Vent manufacturer's instructions.( refer fig. Nº 7)
Attach enough piping to penetrate and extend at least 6" beyond exterior walls. An 8-foot
vertical pipe run is suggested where possible to reduce the possibility of smoke s pillage in the
event of a loss of negative pressure.
Attach cap and seal outside wall thimbles with
non-hardening waterproof mastic.
Termination should not be located so that hot
exhaust gases can ignite trees, shrubs, or grasses or
be a hazard to children.
temperatures of 500ºF and cause serious burns if
touched.
OPTIONAL
HOUSE
SHIELD
SQUARE
HORIZONTAL
CAP
Exhaust gases can reach
Fig 6. Locate terminations: a) not
less than 3 feet above any forced
air inlet located with 10 feet; b)
not less than 4 feet below or
horizontally from, or on foot
above, any door, window or
gravity air inlet into any building;
c) not less than two feet from
an adjacent building and not
less than 7 feet above grade
when located adjacent to a
public walkway. Mobile home
installations must use a spark
arrester.
fig. Nº6
GALVANIZED EXTERIOR
(STAINLESS STEELFOR
CORVENT)
BLACK
fig. Nº7
INTERIOR
-11-