4: User Configurable Items - IBM 3000XLV Operation And Setup Manual

Uninterruptible power supply
Hide thumbs Also See for 3000XLV:
Table of Contents

Advertisement

4: U
C
SER
ONFIGURABLE
N
: S
OTE
ETTINGS ARE MADE THROUGH THE SUPPLIED
THE NETWORK INTERFACE CONNECTION
F
UNCTION
Automatic Self-Test
Every 14 days
(336 hours)
UPS ID
UPS_IDEN
Date of Last Battery
Manufacture Date
Replacement
Minimum Capacity
0 percent
Before Return from
Shutdown
Voltage Sensitivity
High
Alarm Control
Enable
Shutdown Delay
90 seconds
Low Battery Warning
2 minutes
Synchronized Turn-on
0 seconds
Delay
I
TEMS
. R
EFER TO THE SOFTWARE HELP GUIDES FOR DETAILS
F
U
S
ACTORY
SER
ELECTABLE
D
C
EFAULT
HOICES
Every 14 days
(336 hours),
Every 7 days
(168 hours),
On Startup Only,
No Self-Test
Up to eight characters
mm/dd/yy
0, 15, 30, 45, 60, 75, 90
percent
High, Medium, Low
Enable, Mute, Disable
90, 180, 270, 360, 450,
540, 630, 0 seconds
2, 5, 8, 11, 14, 17, 20,
23 minutes
0, 60, 120, 180, 240,
300, 360, 420 seconds
15
P
C
OWER
HUTE SOFTWARE OR
D
ESCRIPTION
This function sets the interval at which the
UPS will execute a self-test.
Use this field to uniquely identify the UPS,
(i.e. server name or location) for network
management purposes.
Reset this date when you replace the inter-
nal battery module.
The UPS will charge its batteries to the
specified percentage before it powers up
connected equipment, following a low-
battery shutdown.
The UPS detects and reacts to line voltage
distortions by transferring to battery power
to protect the connected equipment. When
power quality is poor, the UPS may fre-
quently transfer to battery power. If the
connected equipment can operate normally
under such line voltage conditions, reduce
the sensitivity setting to conserve battery's
capacity and service life.
User can mute an ongoing alarm or disable
all existing alarms permanently.
The interval is set between the times when
the UPS receives a shutdown command and
when it shuts off power to the outlets.
PowerChute software provides automatic,
unattended shutdown when the remaining
battery runtime matches this setting while
on battery.
Change the low battery warning interval
default setting to the time that the operating
system or system software requires to
safely shut down.
The UPS will wait the specified time after
the return of utility power before turn-on
(to avoid branch circuit overload).
.