TABLE OF CONTENTS Safety..............................1 Introduction...........................5 1: INSTALLATION..........................5 Unpacking .............................5 Rail Installation..........................5 Positioning the UPS ........................5 Mounting the UPS in a Rack ......................6 Installing and Connecting the Battery and Attaching the Front Bezel..........6 Tower Configuration ........................7 Connecting Equipment and Power to the UPS................8 Setting the Nominal Voltage......................9 Startup ............................9 Remote Emergency Power Off Switch ..................10...
AFETY Before installing this product, read the Safety Information. Antes de instalar este produto, leia as Informações de Segurança. Pred instalací tohoto produktu si prectete prírucku bezpecnostních instrukcí. Læs sikkerhedsforskrifterne, før du installerer dette produkt. Lees voordat u dit product installeert eerst de veiligheidsvoorschriften. Ennen kuin asennat tämän tuotteen, lue turvaohjeet kohdasta Safety Infor- mation.
Page 4
Prima di installare questo prodotto, leggere le Informazioni sulla Sicurezza. Les sikkerhetsinformasjonen (Safety Information) før du installerer dette produktet. Antes de instalar este produto, leia as Informações sobre Segurança. Antes de instalar este producto, lea la información de seguridad. Läs säkerhetsinformationen innan du installerar den här produkten.
Page 5
CAUTION! Handling Safety - Use safe practices when lifting. <18 kg (<40 lb) 32–55 kg (70–120 lb) 18–32 kg (40–70 lb) >55 kg (>120 lb) >10º CAUTION! Electrical Safety Electrical Current from power, telephone, and communication cables is hazardous. Please read the following safety statements.
Page 6
• Total leakage current from connected equipment and the UPS must not exceed 3.5 mA for a pluggable A Type UPS. CAUTION! De-energizing Safety • The UPS has an internal energy source, the battery. The output may be energized when the unit is not connected to a utility power outlet.
® The IBM UPS 3000XLV and UPS 3000XHV models are designed to prevent blackouts, brownouts, sags, and surges from reaching your computer and other valuable electronic equipment. The uninter- ruptible power supply (UPS) filters small utility line fluctuations and isolates your equipment from large disturbances by internally disconnecting from the utility line.
Mounting the UPS in a Rack Note: Illustrations in this document might differ slightly from your hardware. Step 1 Step 2 Connect the display bezel. Attach the mounting brackets. Flat Head Rear: Connect 8-32 x .375” Step 3 Step 4 To lighten the UPS, remove the battery mod- Install the UPS at or near the bottom of the ule before mounting.
Tower Configuration Step 1 Step 2 Connect the battery to the UPS and attach Remove the rail guides from the UPS. the front bezel. Philips Pan Head 10-32 x .3125” Step 3 Step 4 Connect the display bezel. Rotate and attach the display bezel. Rear: Connect Step 5 Step 6...
Serial Port & USB Port Power management software and interface kits can be used with the UPS. Use only interface kits supplied or approved by IBM. Use the supplied serial cable to connect to the serial port. DO NOT use a standard serial interface cable since it is incompatible with the UPS connector.
This will enable the UPS to start with the proper output voltage. The 3000XLV UPS is able to output 100, 110, 120 and 127V; and the 3000XHV is able to output 200, 208, 220, 230 and 240V. To ensure that the UPS output is centered at or near a voltage that the user requires, set this selection switch appropriately.
Remote Emergency Power Off Switch The UPS can be de-energized with a Remote Emergency Power Off Switch. These switches are in- stalled in situations where, for safety reasons, power to the loads must be quickly disconnected. An electrical connection between Pin 1 and Pin 2 will initiate an immediate Power Off of the UPS. The UPS will not restart until the connection is broken.
UPS 3000XLV and IBM UPS 3000XHV. Field Replaceable Unit Part Numbers IBM FRU part numbers are subject to change without notice. This section contains a listing of the FRU part numbers available at the time this document was published. Rail Kit...
3: O PERATION Front Display Panel Load Battery Charge Test NDICATOR ESCRIPTION Online This LED illuminates when the UPS is supplying utility power to the connected equip- ment. If not illuminated, the UPS is either not turned on, or is supplying battery power. When blinking, the UPS is running an internal self-test.
The VA and power limits depend on the nominal voltage of the UPS. Maximum Power Output UPS and Volt Volts x Amp Watts 3000XLV 100V 2400 2400 3000XLV 110V 2600 2600...
On Battery Operation The UPS switches to battery operation automatically if the utility power fails. While running on bat- tery, an alarm beeps four times every 30 seconds. Press the button to silence this UPS alarm. If the utility power does not return, the UPS contin- ues to supply power to the connected equipment until the battery is fully discharged.
4: U ONFIGURABLE TEMS ETTINGS ARE MADE THROUGH THE SUPPLIED OWER HUTE SOFTWARE OR THE NETWORK INTERFACE CONNECTION EFER TO THE SOFTWARE HELP GUIDES FOR DETAILS ACTORY ELECTABLE UNCTION ESCRIPTION EFAULT HOICES Automatic Self-Test Every 14 days Every 14 days This function sets the interval at which the (336 hours) (336 hours),...
Page 18
ETTINGS ARE MADE THROUGH THE SUPPLIED OWER HUTE SOFTWARE OR THE NETWORK INTERFACE CONNECTION EFER TO THE SOFTWARE HELP GUIDES FOR DETAILS ACTORY ELECTABLE UNCTION ESCRIPTION EFAULT HOICES High Transfer Point 100V: 100V: If the utility voltage is usually high and the 108VAC 108, 110, 112, 114VAC connected equipment is specified to operate...
Refer to Mounting the UPS in a Rack (Step 3) for instructions on battery removal. For replacement, refer to Installing and Connecting the Battery and Attaching the Front Bezel. Be sure to deliver the spent battery to a recycling facility or send it to IBM in the replacement battery packing material.
If the UPS or the component is under warranty, repairs are free. If not, there is a repair charge. 3. Pack the UPS or the faulty component in packaging sent by IBM, and use the return label to ship back to IBM. Pack the UPS properly to avoid damage in transit. Never use Styrofoam beads for packaging.
6: T ROUBLESHOOTING Use the chart below to solve minor UPS installation and operation problems. Refer to IBM for assis- tance with complex UPS problems. ROBLEM AND OSSIBLE OLUTION AUSE UPS WILL NOT TURN ON UPS not connected to utility Check that the power cord from the UPS to the utility power supply is se- power supply.
Page 22
‘3’) are shut off via the net- change them accordingly and review security settings (password, etc.). work interface connection. 3000XLV only: One or more The three outlet groups are individually protected by circuit breakers, in of the outlet groups are over- some cases lower than the overall limit of the UPS.
Page 23
24 hours to confirm the replace battery condition. The alarm stops and the LED clears if the battery passes the self-test. (3000XLV ONLY) THE SITE WIRING FAULT LED ON THE REAR PANEL IS ILLUMINATED Wiring faults detected include missing ground, hot-neutral polarity reversal, The UPS is plugged into an and overloaded neutral circuit.
Page 24
Check that the room temperature is within the specified limits for operation. the UPS has exceeded the Check that the UPS is properly installed, allowing for adequate ventilation. allowable threshold for safe operation. Allow the UPS to cool down. Restart the UPS. If the problem continues, contact IBM.
Properly shielded and grounded cables and connectors must be used in order to meet FCC emission limits. IBM is not respon- sible for any radio or television interference caused by using other than recommended cables and connectors or by unauthor- ized changes or modifications to this equipment.
Any references in this publication to non-IBM Web sites are provided for convenience only and do not in any manner serve as an endorsement of those Web sites. The materials at those Web sites are not part of the materials for this IBM product, and use of those Web sites is at your own risk.