Setting the Nominal Voltage

Before the UPS is connected to utility power, select the appropriate voltage via the voltage selection
switch, located on the rear panel. This will enable the UPS to start with the proper output voltage.
The 3000XLV UPS is able to output 100, 110, 120 and 127V; and the 3000XHV is able to output 200,
208, 220, 230 and 240V. To ensure that the UPS output is centered at or near a voltage that the user
requires, set this selection switch appropriately. (Default voltages are pictured below.)
If this is not done before UPS startup, turn off the UPS, set voltage and restart. Loads connected be-
forehand might not have optimal voltage.
3000XLV Model
While operating on battery, the output voltage equals that of the actual voltage setting dialed. While
operating online, the output voltage is regulated to a range around the nominal voltage. The upper
and lower limits of this range can be user-configured through PowerChute. The input voltage range
can vary while the UPS regulates output without going to battery, and is wider than the regulated
output voltage because of the UPS regulating transformer.

Startup

1. Connect equipment to the UPS.
Note: A laser printer draws significantly more power than other types of equipment and
may overload the UPS.
2. Using the supplied power cord, plug the UPS into a two-pole, three-wire, grounded receptacle
only. Avoid using extension cords. Upon utility power outlet connection, the UPS will auto-
matically turn on.
3000XLV: The power cord is permanently attached to the rear panel of the UPS. The input plug
is a NEMA L5-30P.
3000XHV: The supplied power cord plugs into the rear panel of the UPS.
3. 3000XLV: Check the site wiring fault LED
the UPS is plugged into an improperly wired utility power outlet (See Troubleshooting).
4. Turn on all connected equipment. To use the UPS as a master on/off switch, be sure all con-
nected equipment is turned on.
5. For optimal computer system security, install PowerChute monitoring software onto all com-
puters powered by the UPS.
3000XHV Model
located on the rear panel. It will be illuminated if
9