Retrieving The Alarm History - IBM 1000 VA LCD Installation And Maintenance Manual

Lcd tower ups
Hide thumbs Also See for 1000 VA LCD:
Table of Contents

Advertisement

Table 8. Configuration settings (continued)
Description
Available settings
Overload alarm level
[10%] [20%] [30%]...[100%]
If 100%, the uninterruptible power supply issues an Output
Overload alarm at load > 100%.
Note: Output Overload Level 1 by default is set to 100% and is
configurable from 10% to 100% in 10% increments through the
LCD setting menu. This enables you to be alerted before the
uninterruptible power supply has reached its rated capacity limits.
Automatic start delay
[Off] [0s] [1s] [2s]...[32767s]
See "Configuring load segments" on page 26.
Automatic on battery
[Off] [0s] [1s] [2s]...[32767s]
shutdown
See "Configuring load segments" on page 26.
Site wiring fault alarm
[Enabled] [Disabled]
Battery low alarm
[Immediate] [2 min] [3 min] [5 min]
If you select a value, the battery low alarm is triggered when the
set amount of backup time (approximately) remains in the
batteries.
Automatic battery tests [Enabled] [Disabled]
See "Running automatic battery tests" on page 28.
Clear alarm history
The number after "Total events" shows how many events are
currently stored in the log. Press the OK button for 1 second to
reset the event count to zero and clear the log.
LCD contrast
[-5], [-4], [-3], [-2], [-1], [+0], [+1], [+2], [+3], [+4], [+5]
The display contrast is adjustable, and the valid range is from -5
to +5. This range covers the maximum adjustment for contrasting
the background with the text in the visual display of the control
panel.
REPO input polarity
[Open] [Closed]
If Open, the normally open contacts activate the alarm when the
contacts close. If Closed, the normally closed contacts activate
the alarm when the contacts open.

Retrieving the alarm history

To retrieve the alarm history through the display, complete the following steps:
1. From the main menu, press the down (
2. Press the down (
3. Press the escape (X) button to return to the previous menu.
menu, and press the OK button.
) button to scroll through the listed events, notices, and
alarms.
) button to scroll to the Alarm History
Chapter 3. Operating the uninterruptible power supply
Default setting
100%
0s for Load Segment 1
1s for Load Segment 2
Off
Enabled for 100 V and
120 V models
Disabled for 230 V model
3 minutes
Enabled
Not applicable
[+0]
Open
25