Chimney Requirements - Heatilator I60 Owner's Manual

Woodburning fireplace
Table of Contents

Advertisement

A. Chimney Requirements
Vertical distances are measured from the base of the fi re-
place as shown in Figure 5.2.
Minimum overall straight height
Minimum height with offset/return
Maximum height
Maximum chimney length between an
offset and return
Maximum distance between chimney
stabilizers`
Double offset/return minimum height
Maximum unsupported chimney length
between the offset and return
Maximum unsupported chimney height
above the fi replace
Maximum unsupported chimney above
roof
Note: A maximum of two pairs of offsets and returns may
be used.
WARNING
Fire Risk
Must maintain 2 in. (51 mm) air clearance
to insulation and other combustible
materials.
Table 5.1
HEIGHT OF CHIMNEY
COMPONENTS
US
Chimney Stabilizer
SL11
Ceiling Firestops
FS538
FS540
Offsets/Returns
SL1130
Roof Flashing
RF570
RF571
Chimney Sections*
SL1106
SL1112
SL1118
SL1136
SL1148
n/a
* Dimensions refl ect effective height.
ft
m
18
5.49
18.5
5.64
90
27.43
20
6.10
35
10.67
24
7.32
6
1.83
35
10.67
6
1.83
in.
mm
Canada
SL4
4-3/4
121
FS538
0
0
FS540
0
0
SL430
14-1/2
368
RF570
0
0
RF571
0
0
SL406
4-3/4
121
SL412
10-3/4
273
SL418
16-3/4
425
SL436
34-3/4
883
SL448
46-3/4
1187
SLA10
16-3/4
425
Heatilator • I60 US-CAN • 4013-202 Rev F • 11/07
To determine the chimney components needed to complete
your particular installation, follow the steps below:
Determine the total vertical height of the fireplace
installation. This dimension is measured from the base of
the fi replace assembly to the point where the smoke exits
the termination cap.
Subtract the effective height of the fi replace assembly from
the overall height of the fi replace installation (measured
from the base of the fireplace to the bottom of the
termination cap).
Refer to Table 5.1 to determine what components must
be selected to complete the fi replace installation.
Determine the number of ceiling fi restops, stabilizers,
roof flashing, etc. required to complete the fireplace
installation.
6 ft (1.8 m) max.
unsupported run
20 ft (6 m) max.
pipe between an
offset & return
Ceiling Firestop
11-10 in./279-254mm
adaptor required in
Canada
55-1/2 in.
(1410 mm)
Effective Height
(bottom of fireplace
to top of starter collar)
Figure 5.2

Chimney Requirements

CAUTION
Do NOT connect this fireplace to a chimney flue
servicing another appliance.
Do NOT connect to any air distribution duct or
system.
6 ft (1.8 m) max.
unsupported chimney
above roof
35 ft (10.7 m)
max. straight
unsupported
chimney height
18.5 ft (5.6 m) min. height/single offset-return
24 ft. (7.3 m) min. height/double offset-return
90 ft (27.4 m) max. height
17