PILOT AND BURNER EXTINGUISH WHILE IN OPERATION
A. No LP (propane) in tank.
Check tank and refill if necessary.
B. Glass frame assembly not installed correctly.
Refer to page 8 in this manual for proper glass frame assembly installment instructions.
C. Defective thermopile or thermocouple.
Check thermopile and thermocouple for proper millivolts.
D. Improper pitch on horizontal vent.
1/4" (6 mm) rise per foot is required on horizontal venting.
E. Inner vent pipe leaking exhaust gases back into firebox.
Check for leaks. Repair if necessary.
F. Improper vent cap installation.
Check for proper vent cap installation. Maximum downward slope of horizontal vent cap is 1/4" (6 mm). Adjust if necessary.
Check vent cap for blockage. Remove debris if necessary.
G. Excessive draft.
GLASS SOOTING
A. Improper log placement.
Refer to log placement instructions on page 20 of this installation manual.
B. Improper venturi setting.
Venturi may need to be opened slightly to allow more air into the gas mix.
C. Improper pitch on horizontal venting.
1/4" (6 mm) rise per foot is required on horizontal venting.
FLAME BURNS BLUE AND LIFTS OFF BURNER
A. Improper Venturi setting.
Venturi may need to be closed slightly.
B. Improper vent cap installation.
Check for proper vent cap installation.
C. Blockage or vent system leaks.
TROUBLESHOOTING