Initial Start Up Gas Line Purge; Direct Ignition Troubleshooting - Empire Comfort Systems DVX36FP32CLN-2 Installation Instructions And Owner's Manual

Direct vent zero clearance gas fireplace heater
Table of Contents

Advertisement

NOTE: UNIT MUST BE PROPERLY GROUNDED FOR ELECTRONIC IGNITION TO FUNCTION.
On initial installation, or after extended periods where the fireplace has not been used, gas lines may require purging.
The installer or qualified service person may use the following purge procedures to prevent the delays that would be
caused by waiting for the lockout periods between tries for ignition.
1. Remove glass door and place away from the fireplace.
2. Turn on gas shut off valve. Follow ignition procedure.
3. If burner does not light after spark sequence has ended,
use an insulated jumper wire (see page 49) between
terminal locations 12 and 13 for fast reset function.
4. Interrupt power for 5 seconds. The green indicator light
will blink 4 times repetitively. Then retry for ignition.

DIRECT IGNITION TROUBLESHOOTING

With proper installation and maintenance, your new Direct Vent Gas Fireplace will provide years of trouble-free service. If you do
experience a problem, refer to the troubleshooting guide below. This guide will assist a qualified service person in the diagnosis of
problems and the corrective action to be taken.
SYMPTOM
No spark when system is turned to "ON" and
reset cycle* has been completed
Main burner will light, but igniter continues
to spark for several seconds and then
locks out (module will show two blinks on
indicator light).
Spark for six (6) seconds at ignitor, but no
ignition of burner.
Spark for six (6) seconds, main burner
lights, but goes out when spark stops.
Main burner lights normally and then goes
out.
30329-0-0312

INITIAL START UP GAS LINE PURGE

PURGE PROCEDURE
Check for 120V between black "hot" line
at control module and "white" return at
module
Disconnect power to fireplace junction box
and check that the "Hot-Black" wire is
connected to the gold receptacle screw
side, and that the "Neutral - White" wire
is connected to the silver screw side. The
green ground must also be secured for
proper operation.
a. Check that gas is turned on and system
purged
b. Check that tips of ignitor are directly
above ports on main burner. Spark is
between electrodes and not from one
electrode to burner.
c. Check for 120V at each coil on the gas
valve and listen for click, indicating gas
valve is opening.
Check for clean ground path between
electrode bracket and fireplace chassis.
Check wiring to wiring diagram label. Check
for broken electrode on high-tension lead
attachment to module.
a. Check thermostat if applicable.
b. Check high-tension lead and connector
for shorts.
c. Refer to installation instructions
troubleshooting guide for issues such
as venting.
5. Allow time for any raw gas to dissipate and repeat steps
3 and 4 until ignition is achieved.
6. Turn burner off and install glass door frame assembly.
7. Test ignition of burner with glass door in place.
CHECK
If 120V not present, check fuse or
circuit breaker or repair wiring leading to
fireplace.
Prior to rewiring the fireplace junction box,
check operation of the control system by
running a grounded extension cord from
another standard wall receptacle outlet to
the fireplace control system. Follow purge
reset procedure above in order to clear the
light codes.
Turn gas on and/or purge system
Position electrodes so tips are directly
above burner port ports and about ¼" to
3 /8" above burner.
If 120V present, but gas valve does not click,
replace gas valve.
Clean, position according to wiring diagram,
and repair defective electric connections.
If all electrical connections are clean and
correct, replace module.
Turn thermostat up to call for heat or
replace
Replace spark electrode assembly
Repair as required.
INSULATED
JUMPER WIRE
ACTION
Page 51