Framing and Finishing
1. Choose unit location.
2. Frame in fireplace with a header across the top. It is important
to allow for finished face when setting the depth of the frame.
3. Attach fireplace to frame using adjustable frame. Preset depth
to suit facing material (adjustable to 1/2", 5/8" or 3/4" depths).
4. Use (8) 1/2" hex-head screws supplied in hardware package,
to screw through slotted holes in drywall strip and then screw
into pre-drilled holes on fireplace side. Measure from face of
fireplace to face of drywall strip to determine final depth.
Vent Pipe Clearance
Note: Maintain one inch (1") of clearance around vertical vent
pipe. See Figure 10. For horizontal vent, maintain a minimum 1"
clearance to the bottom and sides of the vent, and 3" clearance to
combustibles above the vent pipe. See Figure 11.
1" MINIMUM CLEARANCE AROUND VENT PIPE
30329-0-0312

INSTALLATION

VENT PIPE
Figure 10
USE OUTER
(4) FLANGES
FOR 1/2"
DRYWALL
Figure 9
Figure 11
Page 11