8. MAINTENANCE

8-1. Address Setting of the Remote
Control Unit
The address can be set in order to prevent
interference between remote controllers when two
Sanyo indoor units are installed near each other. The
address is normally set to "A." To set a different
address, it is necessary to change the address on the
second remote controller.
NOTE
Once changed, you cannot restore the original
address setting of the air conditioner.
Switching the remote controller address
(1) Open the cover on the bottom of the remote
controller. Break the address change tab to switch
the address to B. (Fig. 13)
(2) Insert dry cell batteries into the remote controller
and attach the cover.
(3) Open the front panel on the stopped indoor unit,
and use a sharp object to press the TEST button
on the main unit controller. Verify that the indoor
unit produces the "beep beep" signal-reception
sound, then release the button. (Fig. 14)
(4) Next, within 5 seconds after the beep sound is
heard from the indoor unit, press the remote con
troller ON/OFF button and verify that the 5 beeps
signal-reception sound occurs again. (Fig. 15)
28
Address-setting
tab
Cover
Fig. 13
FILTER
RESET
RESET
/
ON
OFF
TEST
Fig. 14
ON/OFF
operation button
Fig. 15
Test button