4. REFRIGERANT FLOW DIAGRAM

4-1. Refrigerant Flow Diagram
Indoor Unit
SAP-KRV94EHDX
SAP-KRV124EHDX
Indoor unit
Insulation of Refrigerant Tubing
IMPORTANT
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a
proper insulation material. The thickness of the insulation
should be a min. 8 mm.
CAUTION
Wide tube
O.D.
9.52 mm
(3/8 ")
Narrow tube
O.D.
6.35 mm
(1/4")
After a tube has been insulated,
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
Outdoor Unit SAP-CRV94EHDX
SAP-CRV124EHDX
Outdoor unit
Wide tube
service
valve
Muffler
Modulator
Narrow
tube
service
valve
Muffler
Strainer
Thickness:
Min. 8 mm
15
Accumulator
4-way
valve
2-way
S
valve
Capillary
tube for
Electric
split flow
expansion
valve
M
Insulation
Wide tube
Cooling cycle
Heating cycle
Defrosting cycle
Thickness:
Min. 8 mm
Narrow tube