4. REFRIGERANT FLOW DIAGRAM

Indoor Unit
SAP – K302AH
Indoor unit
Insulation of Refrigerant Tubing
IMPORTANT
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a
proper insulation material. The thickness of the insulation
should be a min. 8 mm.
CAUTION
Wide tube
service
Wide tube
valve
O.D.
ø15.88 mm
(5/8 ")
Narrow tube
O.D.
ø9.52 mm
(3/8")
After a tube has been insulated,
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
Outdoor Unit
Outdoor unit
Muffler
Narrow
tube
service
valve
Strainer
Capillary tube
8
SAP – C302AH
Accumulator
4-way
valve
Insulation
Thickness:
Min. 8 mm
Wide tube
Cooling cycle
Heating cycle
Thickness:
Min. 8 mm
Narrow tube