VISTA-32FB/VISTA-128FB Installation and Setup Guide

Event Log Connections

This system has the ability to record up to 512 events of
various categories in the Event Log (history log). Each
event is recorded with the time and date of its
occurrence (if real-time clock is set).
The categories are Alarm, Supervisory/Check, Bypass,
Open/Close, System and Test conditions. The log may
be viewed on an alpha keypad or printed on a serial
printer.
x When using a printer, field 3*19 must be set
to a 1.
x The serial printer must be configured with 7
data bits, even parity, 1 stop bit, and either
300 or 1200 baud.
Connecting the Serial Printer
To connect a serial printer, refer to Figure 3-30 and
perform the following steps:
Step
Action
Connect the 4142TR cable to J2 on the
1
control.
Connect the Violet and Red wires of the
2
4142TR to terminal 1 and 6 on the 4100SM,
respectively.
Connect terminals 8 and 7 of the 4100SM to
3
terminals 11 and 12 (aux. power (+) and (-)),
respectively of the control.
Connect the serial printer to the 4100SM.
4
NOTE: The 4100SM Module is supplied with
a 10-foot RS232 cable. A longer cable can be
used if the VISTA-32FB/VISTA-128FB is
separated from the serial printer by more
than 10 feet, but the total cable length should
be less than 50 feet.

Installing the 4285/4286 VIP Module

The 4285/4286 VIP Module is an add-on accessory that
permits the user to access the security system (and
relays) via a TouchTone telephone. This may be done
either from the premises or by calling the premises
from a remote location. Only one VIP Module can be
used in a security system. This module must be
enabled as Device Address 4 in the Device
Programming in #93 Menu Mode, and must be assigned
to a partition.
The 4285/4286 VIP Module is not permitted in
U L
UL installations.
Detailed operating instructions for phone access
to the security system are provided with the VIP
Module.
3-26
1
2
3
4
5
6
7
8
9
4142TR CABLE (SUPPLIED WITH 4100SM)
To TB11 Aux. Power (+)
(25mA current draw)
To TB12 Aux. Power (-)
4100SM JUMPERS
(CUT TO SET RESPECTIVE SIGNAL FLOATING)
COLOR
FUNCTION
PIN #
RED
CD
8
BLUE
CTS
5
WHITE
DSR
6

Figure 3-30: Printer Connections to the 4100SM

NOTE: See the 4100SM Installation Instructions for
details concerning the serial printer operation.
The 4285/4286 VIP Module features:
x
Allows the user to receive synthesized voice
messages over the phone regarding the status of
the security system.
x
Allows the user to arm and disarm the security
system and perform most other commands using
the telephone keypad.
x
Allows the user to control relays using the
telephone keypad.
Provides voice annunciation over the phone to
x
confirm any command that is entered.
x
Announces many of the same words that would
normally be displayed on an alpha keypad under
the same system conditions. Refer to the words in
bold on the Alpha Vocabulary list found in the #93
Menu Mode Programming in the Programming
Guide.
x
Can be supervised for connection to control panel
(annunciated and reported as Zone 804).
J2 CONNECTOR
4100SM SERIAL MODULE
8
+ PWR
- (GND)
7
6
RXD
5
not used
4
not used
3
TXD
2
not used
DTR
1
RED
BLUE
WHITE
USE GENDER CHANGER
3M
Cable
SUPPLIED WITH 4100SM
Supplied with
IF PRINTER HAS DB25
4100SM
MALE CONNECTOR
SERIAL PRINTER
SET FOR: 8 DATA BITS
EVEN PARITY
STOP BIT
300/1200 BAUD