Clearances - MHSC STLDVNS Installation And Operating Instructions Manual

Designer series direct vent gas fireplace
Table of Contents

Advertisement

CLeaRaNCeS

CLeaRaNCeS To CoMBuSTIBLeS
Follow these instructions carefully to ensure safe installation. Failure to
follow instructions exactly can create a fire hazard.
The appliance cannot be installed on a carpet, tile or other combustible
material other than wood flooring. If installed on carpet or vinyl flooring, the
appliance shall be installed on a metal, wood or noncombustible material
panel extending full width and depth of the appliance.
72"
(1829 mm)
Min.
6"
(152 mm)
Min.
Figure 9 -
Ceiling and Side Wall Clearances
MaNTeL CLeaRaNCeS
FP2832
NoTe: The combustible area above the facing must
ceiling wall clearance
not protrude more than 1/2" from the facing. If it does,
it is considered a mantel and must meet the mantel
requirements listed in this manual.
Never obstruct or modify the air inlet or
outlet grilles (louvers). This may create
a fire hazard.
20302381
Combustible Mantel
12"
(305 mm)
Max. Depth
16"
(406 mm)
Min.
FP2544
Designer Series Direct Vent Gas Fireplace
12"
6"
16"
12"
10"
Top of Fireplace
Opening
Side View
FP2818
Top View
Side of Fireplace
Opening
Figure 10 -
FP2818
Mantel Clearance
mantel leg clearance
Noncombustible
Material to Top of
Standoffs
2 "
FP2817
Spacer
FP2817
mantel clearances
Stud
Combustible
Material Area
1"
"
3"
4"
5"
6"
45°
13