VeNTING INSTaLLaTIoN
VeRTICaL ThRouGh-The-RooF aPPLICa-
TIoNS
a restrictor disc must be installed on
vertical terminations that are higher than
12' (366 cm).
Install restrictor disc as shown in Figure 34 for vertically
vented applications.
Up to two (2) restrictor discs may be needed for 40' instal-
lation.
The two (2) restrictor discs suppled will work for most instal-
lations. If a third disc is needed order Part No. 56D3027.
You may use a reducer to 4" x 6B\," or
4" x 7" in vertically vented applica-
tions. If a reducer is used, only one
restrictor may be used.
Figure 34 -
Install Restrictor Disc
into Fireplace Collar
This gas fireplace has been approved for,
Vertical installations up to 40' (12 m) in height. Up to
a 10' (3 m) horizontal vent run can be installed within
the vent system using a maximum of two 90° elbows.
Figure 35
NoTe: Horizontal sections of this vent system require a
minimum of 3" clearances to combustibles at the top of
the flue and 1" clearance at the sides and bottom until the
flue penetrates the outside wall. A minimum 1" clearance
all around the flue is acceptable at this point of penetration.
Unless the vertical run is 7Z\x feet or higher form floor of
fireplace, the clearance for the horizontal run is 1" on all
sides.
Vertical sections of this vent system require a minimum of
1" clearance to combustibles on all sides of the pipe.
Up to two 45° elbows may be used within the horizontal
run. For each 45° elbow used on the horizontal plane,
the maximum horizontal length must be reduced by 18"
(457 mm).
20302381
Restrictor
Disc
Fireplace
Collar
FP2839
FP2839
restrictor disc
Designer Series Direct Vent Gas Fireplace
40' Maximum Height
8' Minimum Height
40' Maximum Height
8' Minimum Height
Figure 35 -
Support Straps for Horizontal Runs
Example: Maximum horizontal length
No elbows = 10' (3 m)
1x45° elbows = 8.5' (2.6 m)
2x45° elbows = 7' (2.1 m)
FP2308
support straps
A minimum of an 8' (2.5 m) vertical rise is required.
Two sets of 45°elbows offsets may be used within the
vertical sections. From 0 to a maximum of 8' (2.5 m)
of vent pipe can be used between elbows. Figure 27
The maximum angular variation allowed in the system
is 270°. Figure 27
The minimum height of the vent above the highest point
of penetration through the roof is 2' (610 mm).
10'
Maximum
Support Straps
Every 3'
10'
Maximum
Support Straps
Every 3'
FP2308
25