Clearances; Mantel Clearances - MHSC CDVR36NV7CE Installation And Operating Instructions Manual

Direct vent gas fireplace cdv7 series
Table of Contents

Advertisement

ClEaRaNCES

CLEARANCES TO COMbUSTIbLES
Follow these instructions carefully to ensure safe installation. Failure to follow
instructions exactly can create a fire hazard.
The appliance cannot be installed on a carpet, tile or other combustible material
other than wood flooring. If installed on carpet or vinyl flooring, the appliance
shall be installed on a metal, wood or noncombustible material panel extending
full width and depth of the appliance.
72"
(1829 mm) 
Minimum
Side
Wall
6"
(152 mm)
Minimum
Figure 4 -
Ceiling and Side Wall Clearances
fP2032
wall clearances

MaNtEl ClEaRaNCES

NotE: The combustible area above the facing must not protrude
more than 3/4" (19 mm) from the facing. If it does, it is considered
a mantel and must meet the mantel requirements listed in this
manual.
Never obstruct or modify the air inlet or
outlet grilles (louvers). This may create
a fire hazard.
69D2027
12"
(305 mm)
Maximum
Depth
13"
(330 mm) 
Minimum
Top of Heat
Exhaust Vent
FP2032
FP2286
Side of Fireplace
Opening
Figure 5 -
Mantel Clearances
CDV7 Series Gas Fireplace
Finish Wall
12" (305 mm)
2 "
(64 mm)
13"
(330 mm)
12"
(305 mm)
Side View
FP2285 36
mantel clearances
1"
1 "
2 "
3"
5"
6"
Front View
FP2286
Mantel leg clear
Stud
Header
Standoff
FP2285
Stud
Wall
Combustible
Material Area
3 "
4 "
45°
9