Installation For Vertical Termination - MHSC STLDVNS Installation And Operating Instructions Manual

Designer series direct vent gas fireplace
Table of Contents

Advertisement

Designer Series Direct Vent Gas Fireplace
1
2
3
4
Example:
Elbow 1 = 90°
Elbow 2 = 45°
Elbow 3 = 45°
Elbow 4 = 90°
Total Angular Variation = 270°
Figure 36 -
Maximum Elbow Usage
INSTaLLaTIoN FoR VeRTICaL TeRMINa-
TIoN
1. Determine the route your vertical venting will take. If
ceiling joist, roof rafters or other framing will obstruct
the venting system, consider an offset. Refer to Figure
32 to avoid cutting load bearing members.
NoTe: Pay special attention to these installation instructions
for required clearances (air space) to combustibles when
passing through ceilings, walls, roofs, enclosures, attic
rafters, etc. Do not pack air spaces with insulation. Also
note maximum vertical rise of the venting system and any
maximum horizontal offset limitations. Offsets must fall
within the parameters shown on Page 19, Figure 18.
2. Set fireplace in desired location. Drop a plumb line down
from the ceiling to the position of the flue exit. Mark the
center point where the vent will penetrate the ceiling.
Drill a small locating hole at this point.
Drop a plumb line from the inside of the roof to the locat-
ing hole in the ceiling. Mark the center point where the
vent will penetrate the roof. Drill a small locating hole
at this point.
26
1
2
3
4
FP2309
max elbow use A
Wall Strap
Figure 37 -
Offset with Wall Strap and 45° Elbows
FLaT CeILING INSTaLLaTIoN
FP1969
offset w/ wallstrap
1. Cut a 10
" (267 mm) square hole in the ceiling using
Z\x
the locating hole as a center point The opening should
be framed to 10
" x 10
Z\x
dimensions as shown in Figure 39 using framing lumber
the same size as the ceiling joist. If the area above the
ceiling is an insulated ceiling or a room, nail firestop
from the top side. This prevents loose insulation from
falling into the required clearance space. Figure 39.
Otherwise, install firestop below the framed hole. The
firestop should be installed with no less than three (3)
nails per side. Figure 38 or 39.
2. Assemble the desired lengths of pipe and elbows nec-
essary to reach from the burner system flue up through
the firestop. Be sure pipe and elbow connections are
fully twist-locked. Page 20, Figure 20.
3. Cut a hole in the roof using the locating hole as a center
point. (Cover any exposed open vent pipes before cut-
ting hole in roof). The 10
hole must be measured on the horizontal. Actual length
may be larger depending on the pitch of the roof. There
must be a 1" minimum clearance from the vent pipe to
combustible materials. (Insulation should be considered
a combustible material). Frame the opening as shown
on Page 20, Figure 21.
4. Connect a section of pipe and extend up through the
hole.
VeNTING INSTaLLaTIoN
Roof
Flashing
45° Elbows
FP1669
Ceiling Firstop
" (267 x 267 mm) inside
Z\x
" x 10
" (267 x 267 mm)
Z\x
Z\x
20302381

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

StldvpsCrldvpsClldvnsCrldvnsPfldvnsPfldvps ... Show all

Table of Contents