Pfdv Framing - MHSC STLDVNS Installation And Operating Instructions Manual

Designer series direct vent gas fireplace
Table of Contents

Advertisement

Designer Series Direct Vent Gas Fireplace
Remove box and
Insulation for Top
Vent Configurations
Figure 7 -
PFDV (Peninsula) Framing
The fireplace must be secured to the floor and/or to framing
studs as shown in Figure 7 . Use four (4) wood screws or
masonry/ concrete screws to secure fireplace to the floor.
Use four (4) screws to attach fireplace to framing. The side
brackets or nailing flanges are designed to accommodate
two wall boards thicknesses, 1/2" or 5/8".
10
46 " (1172 mm)
(1/2" Drywall)
or
46" (1168 mm)
(5/8" Drywall)
FP2850
Peninsula framing
FIRePLaCe FRaMING
23" (584 mm)
(1/2" Drywall)
or Adjustable to
22 " (578 mm)
(5/8" Drywall)
Noncombustible
Material
48
(1224 mm)
If using 5/8" drywall,
remove drywall supports,
rotate 180° and reinstall
The area above and on the sides of the
fireplace must be a noncombustible material.
Figures 5, 6, 7
Never install combustible materials over
front face of fireplace.
If using 5/8" drywall, remove
framing tabs and re-install
on 2nd set of holes
positioned slightly inwards
Fold Outer Tabs
and Nail to Framing
Members
20302381