Alarm And Alert Codes - Carrier 30GTN Service And Troubleshooting Manual

Air-cooled reciprocating with comfortlink controls 50/60 hz controls, start-up, operation, service, and troubleshooting
Table of Contents

Advertisement

ALARM/
ALARM
ALERT
OR
DESCRIPTION
CODE
ALERT
51
Alert
Circuit A, Compressor 1
Failure
52
Alert
Circuit A, Compressor 2
Failure
53
Alert
Circuit A, Compressor 3
Failure
54
Alert
Circuit A, Compressor 4
Failure
55
Alert
Circuit B, Compressor 1
Failure
56
Alert
Circuit B, Compressor 2
Failure
57
Alert
Circuit B, Compressor 3
Failure
60
Alarm
Cooler Leaving Fluid
Thermistor Failure (T1)
61
Alarm
Cooler Entering Fluid
Thermistor Failure (T2)
64
Alert
Circuit A Saturated Con-
densing Thermistor Fail-
ure (T3)
65
Alert
Circuit B Saturated Con-
densing Thermistor Fail-
ure (T4)
66
Alert
Circuit A Saturated Suc-
tion Thermistor Failure
(T5)
67
Alert
Circuit B Saturated Suc-
tion Thermistor Failure
(T6)
68
Alert
Compressor A1 Suction
Gas Thermistor Failure
(T7)
69
Alert
Compressor B1 Suction
Gas Thermistor Failure
(T8)
73
Alert
Outside Air Thermistor
Failure (T9)
74
Alert
Space Temperature
Thermistor Failure (T10)
77
Alert
Circuit A Saturated
Suction Temperature
exceeds Cooler Leaving
Fluid Temperature
78
Alert
Circuit B Saturated
Suction Temperature
exceeds Cooler Leaving
Fluid Temperature
Table 27 — Alarm and Alert Codes
WHY WAS THIS
ALARM
GENERATED?
Compressor feedback
Circuit A shut down.
signal does not match
relay state
Compressor feedback
Circuit A shut down.
signal does not match
Circuit restarted in 1
relay state
minute. Compressor
A2 not used until alarm
is reset.
Compressor feedback
Circuit A shut down.
signal does not match
Circuit restarted in 1
relay state
minute. Compressor
A3 not used until alarm
is reset.
Compressor feedback
Circuit A shut down.
signal does not match
Circuit restarted in 1
relay state
minute. Compressor
A4 not used until alarm
is reset.
Compressor feedback
Circuit B shut down.
signal does not match
relay state
Compressor feedback
Circuit B shut down.
signal does not match
Circuit restarted in 1
relay state
minute. Compressor
B2 not used until alarm
is reset.
Compressor feedback
Circuit B shut down.
signal does not match
Circuit restarted in 1
relay state
minute. Compressor
B3 not used until alarm
is reset.
Thermistor outside
Chiller shutdown after
range of −40 to 245 F
pumpdown complete.
(−40 to 118 C)
Thermistor outside
Chiller shutdown after
range of −40 to 245 F
pumpdown complete.
(−40 to 118 C)
Thermistor outside
Circuit A shutdown
range of −40 to 245 F
after pumpdown com-
(−40 to 118 C)
plete. (EXV only)
Thermistor outside
Circuit B shutdown
range of −40 to 245 F
after pumpdown
(−40 to 118 C)
complete.
Thermistor outside
Circuit A shutdown
range of −40 to 245 F
after pumpdown com-
(−40 to 118 C)
plete. (EXV only)
Thermistor outside
Circuit B shutdown
range of −40 to 245 F
after pumpdown
(−40 to 118 C)
complete.
Thermistor outside
Circuit A shutdown
range of −40 to 245 F
after pumpdown com-
(−40 to 118 C)
plete. (EXV only).
Thermistor outside
Circuit B shutdown
range of −40 to 245 F
after pumpdown com-
(−40 to 118 C)
plete. (EXV only).
Thermistor outside
Temperature reset dis-
range of −40 to 245 F
abled. Chiller runs un-
(−40 to 118 C)
der normal control/set
points.
Thermistor outside
Temperature reset dis-
range of −40 to 245 F
abled. Chiller runs un-
(−40 to 118 C)
der normal control/set
points.
Saturated suction is
Circuit A shutdown
greater than leaving
after pumpdown
fluid temperature for
complete.
more than 5 minutes
Saturated suction is
Circuit B shutdown
greater than leaving
after pumpdown
fluid temperature for
complete
more than 5 minutes
48
ACTION TAKEN
RESET
BY CONTROL
METHOD
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
PROBABLE
CAUSE
High-pressure or loss-of-
charge switch open, faulty
control relay or CPCS
board, loss of condenser
air, liquid valve closed, op-
eration beyond capability.
High-pressure switch open,
faulty control relay or CPCS
board, loss of condenser
air, liquid valve closed, op-
eration beyond capability.
High-pressure switch open,
faulty control relay or CPCS
board, loss of condenser
air, liquid valve closed, op-
eration beyond capability.
High-pressure switch open,
faulty control relay or CPCS
board, loss of condenser
air, liquid valve closed, op-
eration beyond capability.
High-pressure or loss-of-
charge switch open, faulty
control relay or CPCS
board, loss of condenser
air, liquid valve closed, op-
eration beyond capability.
High-pressure switch open,
faulty control relay or CPCS
board, loss of condenser
air, liquid valve closed, op-
eration beyond capability.
High-pressure switch open,
faulty control relay or CPCS
board, loss of condenser
air, liquid valve closed, op-
eration beyond capability.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Faulty expansion valve or
EXV board, faulty cooler
suction thermistor (T5) or
leaving fluid thermistor (T1).
Faulty expansion valve or
EXV board, faulty cooler
suction thermistor (T6) or
leaving fluid thermistor (T1).