Carrier 30GTN Service And Troubleshooting Manual page 73

Air-cooled reciprocating with comfortlink controls 50/60 hz controls, start-up, operation, service, and troubleshooting
Table of Contents

Advertisement

DESCRIPTION
1
FSM controlling chiller
2
WSM controlling chiller
3
Master/Slave control
4
Low source protection
5
Ramp Load Limited
6
Timed Override in effect
7
Low Cooler Suction TempA
8
Low Cooler Suction TempB
9
Slow Change Override
10
Minimum OFF Time
11
Low Suction Superheat A
12
Low Suction Superheat B
13
Dual Setpoint
14
Temperature Reset
15
Demand Limit in effect
16
Cooler Freeze Prevention
17
Lo Tmp Cool/Hi Tmp Heat
18
Hi Tmp Cool/Lo Tmp Heat
DESCRIPTION
1
COOLING
2
Cool Setpoint 1
3
Cool Setpoint 2
4
RAMP LOADING
5
Cooling Ramp Loading
6
HEAD PRESSURE
7
Head Press. Stpt A
8
Head Press. Stpt B
DESCRIPTION
1
(SYSTEM PRIMARY MESSAGE)
2
(SYSTEM SECONDARY MESSAGE)
3
Machine Operating Hours
4
Entering Chilled Water
5
Leaving Chilled Water
6
Control Point
7
Percent Total Capacity
8
Active Demand Limit
9
Operating Setpoint
10
Circuit A Total Cap
11
Circuit B Total Cap
12
Machine Starts
CURRMODS
STATUS
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
SETPOINT
STATUS
−20 to 70
−20 to 70
0.2 to 2.0
80 to 140
80 to 140
LID DEFAULT SCREEN DEFINITION
TABLE TYPE 19 HEX
STATUS
nnnnn
snnn.n
snnn.n
snnn.n
0-100
0-100
snnn.n
0-100
0-100
nnnnn
73
UNITS
UNITS
POINT
°F
CSP1
°F
CSP2
°F/min
CRAMP
°F
HSP A
°F
HSP B
UNITS
POINT
hours
HR MACH
°F
EWT
°F
LWT
°F
CTRL PNT
%
CAP T
%
DEM_LIM
°F
SP
%
CAPA T
%
CAPB T
CY MACH
POINT
MODE 1
MODE 2
MODE 3
MODE 4
MODE 5
MODE 6
MODE 7
MODE 8
MODE 9
MODE 10
MODE 11
MODE 12
MODE 13
MODE 14
MODE 15
MODE 16
MODE 17
MODE 18
DEFAULTS
44
44
1.0
113
113
DISPLAY
HR MACH
EWT
LWT
CTRL PNT
CAP T
DEM_LIM
SP
CAPA T
CAPB T
CY MACH