Carrier 30GTN Service And Troubleshooting Manual page 69

Air-cooled reciprocating with comfortlink controls 50/60 hz controls, start-up, operation, service, and troubleshooting
Table of Contents

Advertisement

DESCRIPTION
1
COOLING RESET
2
Cooling Reset Type
3
No Cool Reset Temp
4
Full Cool Reset Temp
5
Degrees Cool Reset
6
DEMAND LIMIT
7
Demand Limit Select
8
Demand Limit at 20mA
9
Loadshed Group Number
10
Loadshed Demand Delta
11
Maximum Loadshed Time
12
Demand Limit Switch 1
13
Demand Limit Switch 2
14
LEAD/LAG
15
Lead/Lag Enable
16
Master/Slave Select
17
Slave Address
18
Lead/Lag Balance Select
19
Lead/Lag Balance Delta
20
Lag Start Delay
DESCRIPTION
1
CCN Time/Date Broadcast
2
CCN OAT Broadcast
3
Global Schedule Broadcst
4
CCN Broadcast Acker
5
Daylight Savings Start
6
Month
7
Week
8
Day
9
Minutes to add
10
Daylight Savings Stop
11
Month
12
Week
13
Day
14
Minutes to subtract
RESETCON (Temperature Reset and Demand Limit)
STATUS
0 = No Reset
1 = 4-20 ma input
2 = External temp-OAT
3 = Return fluid
4 = External temp-SPT
0 to 125
0 to 125
−30 to 30
0 = None
1 = External switch input
2 = 4-20 ma input
3 = Loadshed
0 to 100
0 to 99
0 to 60
0 to 120
0 to 100
0 to 100
Enable/Disable
Slave/Master
0 to 239
Enable/Disable
40 to 400
0 to 30
BRODEFS (Broadcast POC Definition Table)
STATUS
Yes/No
Yes/No
Yes/No
Yes/No
1 to 12
1 to 5
1 to 7
0 to 99
1 to 12
1 to 5
1 to 7
0 to 99
DEFAULT
0
0.0
125.0
0.0
0
100
0
0
60
80
50
Disable
Master
0
Disable
168
5
DEFAULT
No
No
No
No
1
1
0
0
1
1
0
0
69
UNITS
POINT
CRST TYP
°F
CT NO
°F
CT FULL
^F
CT DEG
DMD CTRL
%
DMT20MA
SHED NUM
%
SHED DEL
min
SHED TIM
%
DLSWSP1
%
DLSWSP2
LL ENA
MS SEL
SLV ADDR
LL BAL
hours
LL BAL D
mins
LL DELAY
UNITS
POINT
CCNBC
OATBC
GSBC
CCNBCACK
STARTM
STARTW
STARTD
min
MINADD
STOPM
STOPW
STOPD
min
MINSUB