Carrier 30GTN Service And Troubleshooting Manual page 39

Air-cooled reciprocating with comfortlink controls 50/60 hz controls, start-up, operation, service, and troubleshooting
Table of Contents

Advertisement

SUB-MODE KEYPAD ENTRY
RSET
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
Table 17 — Example of Configuring Dual Chiller Control
ITEM
DISPLAY
ITEM EXPANSION
CRST
0
LLDY
5
LAG START DELAY
5
5
10
10
LLDY
10
LLBD
168
LEAD/LAG BALANCE DELTA
LLBL
DSBL
LEAD/LAG BALANCE SELECT
DSBL
DSBL
ENBL
ENBL
LLBL
ENBL
SLVA
0
SLAVE ADDRESS
0
0
6
6
SLVA
6
MSSL
MAST
MASTER/SLAVE SELECT
LLEN
DSBL
LEAD/LAG CHILLER ENABLE
DSBL
DSBL
MAST
LLEN
MAST
LLEN
MAST
LEAD/LAG CHILLER ENABLE
Scrolling stops
Value flashes
Select 10
Change accepted
No change needed. Default set for weekly changeover
Scrolling stops
Value flashes
Select Enable
Change accepted
Scrolling stops
Value flashes
Select 6
Change accepted
No change needed. Default set for Master
Scrolling stops
Value flashes
Select Master
Change accepted
Item/Value/Units scrolls again