Carrier 30GTN Installation Instructions Manual
Carrier 30GTN Installation Instructions Manual

Carrier 30GTN Installation Instructions Manual

Energy management module

Advertisement

Quick Links

CONTENTS
SAFETY CONSIDERATIONS
INTRODUCTION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
Install Harness and Make Wire
Connections
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Configure Control (All Sizes)
Temperature Reset (4 to 20 mA)
Demand Limit (4 to 20 mA)
Demand Limit (Switch Controlled)
SAFETY CONSIDERATIONS
Installation of this accessory can be hazardous due to sys-
tem pressures, electrical components, and equipment location
(such as a roof or elevated structure).
Only trained, qualified installers and service technicians
should install, start up, and service this equipment (Fig. 1).
When installing this accessory, observe precautions in the
literature, labels attached to the equipment, and any other
safety precautions that apply.
Follow all safety codes.
Wear safety glasses and work gloves.
Use care in handling and installing this accessory.
ELECTRIC SHOCK HAZARD.
To avoid the possibility of electrical shock,
open and tag all disconnects before installing
this equipment.
INTRODUCTION
The Energy Management Module Accessory (EMM) pack-
age is required for additional Temperature Reset, Demand
Limit, and Ice Done features of the ComfortLink™
30GTN,GTR and 30GUN,GUR chillers. Temperature Reset
function by return water, outside air or space temperature do
NOT require the addition of this accessory. The following ad-
ditional features are supported by this accessory:
temperature reset by 4 to 20 mA field supplied signal.
demand limit control via field supplied two-step switch
input.
demand limit control via field supplied 4 to 20 mA
signal.
support of unoccupied operation for ice making through
field supplied contacts.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
PC 903
Tab 5c
Installation Instructions
Part Number 30GT-911---060
. . . . . . . . . . . . . . . . . . . 1
. . . . . . . . . . . . . . . . . . 7
. . . . . . . . . . . . . . . 8
. . . . . . . . . . . . . . . . . . . . 9
. . . . . . . . . . . 10
Catalog No. 533-076
Printed in U.S.A.
30GTN,GTR,GUN,GUR040-420
Energy Management Module (EMM)
Accessory Package Contents
ITEM
Energy Management Module,
30GT515218
Terminal Block, HY84FE029
3
Screws, no. 6
/
-in. long
4
Screws, no. 10
3
/
-in. long
4
Harness Assembly, 30GT415088
Harness Assembly, 30GT415224
INSTALLATION
1. Inspect the package contents for missing or damaged
parts. File a claim with shipping agency if parts are
damaged. Notify your Carrier representative if any
items are missing.
2. Open and tag all electrical disconnects.
3. Open the left side control box door to access the con-
trol wiring side of box.
4. Using the five no. 6 screws provided in the package,
mount the EMM in the pre-drilled holes in the control
panel near the lower left corner of the display/fuse
bracket. See Fig. 2. Using the two no. 10 screws pro-
vided in the package, mount the terminal block above
the EMM board.
5. For size 130-210 machines (and modules 230A-420A,
330B-420B), mount the EMM board above TB5. See
Fig. 3.
6. The board addresses are set through 4-position DIP
switches. All switches are set to ON for all boards. See
Fig. 1.
Install Harness and Make Wire Connec-
tions —
Locate harness supplied with accessory. use the
30GT415088 harness for 040-110 sizes (and modules 230B-
315B). Use the 30GT415224 harness for 130-210 sizes (and
modules 230A-420A and 330B-420B).
Make four plug connections at the EMM using the connec-
tors labeled EMM-J1, J4, J6, and J7. See Fig. 4 and 5.
Two remaining plug connections need to be made. Connect
the plug labeled 30GT415224 at the Main Base Board (MBB)
for all 040-110 sizes. Connect the plug labeled EXV-J3/MBB-
J3 at the Expansion Valve Board (EXV), if installed for 040-
110 sizes. Otherwise, connect the plug to the Main Base Board
(MBB). See Fig. 4.
For sizes 130-210 connect the plug labeled MBB-J2/
CXB-J2 to the Main Base board (MBB) or to the Expansion
Board (CXB, if installed) and connect the plug labeled EXV-J3
CXB-J3 at the Expansion Board (CXB, if installed). Other-
wise, connect the plug to the Expansion Valve Board (EXV).
See Fig. 5.
Form 30GTN-3SI
Accessory
50/60 Hz
QUANTITY
1
1
5
2
1
1
Pg 1
6-99
Replaces: New

Advertisement

loading

Summary of Contents for Carrier 30GTN

  • Page 1 1. Inspect the package contents for missing or damaged parts. File a claim with shipping agency if parts are Installation of this accessory can be hazardous due to sys- damaged. Notify your Carrier representative if any tem pressures, electrical components, and equipment location items are missing.
  • Page 2 CEBD430351-0396-01C STATUS TEST 2 GREEN LED - ADDRESS RED LED - STATUS LEN (LOCAL EQUIPMENT NETWORK) DIP SWITCHES Fig. 1 — EMM Board...
  • Page 3 LEGEND — Carrier Comfort Network — Cooler Heater Thermostat CLHR — Cooler Heater Relay CPSC — Compressor Protection and Control System — Expansion Board Accessory — Energy Management Module EQUIP GND — Equipment Ground — Electronic Expansion Valve — Fuse Block FIOP —...
  • Page 4 LEGEND — Compressor Ground Fault — Cooler Heater Thermostat CLHR — Cooler Heater Relay — Control Relay — Expansion Board Accessory — Energy Management Module EQUIP GND — Ground — Electronic Expansion Valve — Fuse Block FIOP — Factory-Installed Option —...
  • Page 5 LEGEND — Circuit Breaker — Electronic Expansion Valve — Space Temperature — Circuit FIOP — Factory-Installed Option — Switch CPCS — Compressor Protection Control Systems — Ground — Terminal Block CWFS — Chilled Water Flow Switch — Main Base Board TEMP —...
  • Page 6 LEGEND — Circuit Breaker — Electronic Expansion Valve — Space Temperature — Circuit FIOP — Factory-Installed Option — Switch CPCS — Compressor Protection Control Systems — Ground — Terminal Block CWFS — Chilled Water Flow Switch — Main Base Board TEMP —...
  • Page 7 Configure Control (All Sizes) Press . Press the up arrow key to select ENTER EMM. Press to stop display at its current 1. The control must be configured to recognize the ENTER Energy Management Module. Using the display, press value, NO. Press again and PASS WORD ENTER until the screen is blank.
  • Page 8 Temperature Reset (4 to 20 mA) — The configuration is now complete. As an example, if the A field sup- cooling set point (CSP.1) is set to 44 F, the control will linearly plied and generated, externally powered 4 to 20 mA signal can reset the control point (CTPT) based on the 4 to 20 mA signal.
  • Page 9 Demand Limit (4 to 20 mA) — The configuration is now complete. There will be no de- A field-supplied and mand limit for a 4 mA signal. If the signal was 20 mA, the generated externally powered 4 to 20 mA signal can be used to chiller capacity (CAP) would be limited to 60%.
  • Page 10 Demand Limit (Switch Controlled) — The configuration is now complete. The overall chiller ca- A field-sup- pacity (CAP, under the Run Status mode, submode VIEW) will plied pair of dry contacts can be used to provide one or two now be reduced to 70% when Demand Limit switch 1 is steps of demand limit.
  • Page 12 Copyright 1999 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. PC 903 Catalog No. 533-076 Printed in U.S.A. Form 30GTN-3SI Pg 12 6-99 Replaces: New Book 2...